This manual provides operation instructions, setting procedures, and troubleshooting guides for the TOYO OVGTOYO-OVG MGV Type meter relay.
This document is the Chinese operation manual for the TOYO OVGTOYO-OVG MGV Type meter relay. It details the device's application in Y-Y OPEN DELTA systems and GPT third winding configurations of 190/3V or 110/3V. The guide covers initial setup, including setting the GPT third winding rating and configuring display parameters. This manual is written in Chinese.
| Applicable System | Y-Y OPEN DELTA system |
|---|---|
| Applicable Voltage | 190/3V or 110/3V |
| Max AC Voltage | 250V |
| Max DC Voltage | 100V |
| Max DC Current | 0.3A |
| Power Supply | 80~264V AC/DC |
| RS-485 Baud Rate | 2400/4800/9600 |
| RS-485 Address Range | 1~247 |
| Zero Phase Alarm Time Range | 0.1~5.0 seconds |
Press and hold the '+' key, then turn on the power to see 190V or 110V. Press '-' or '+' to select the rated value, then press the key to complete.
In Auto mode, the backlight turns on during operation and turns off automatically after a period of time.
It indicates that the input signal exceeds the set upper or lower limits.
Press the SET and '+' keys together to reset the zero phase voltage alarm and the maximum/minimum values for each phase.