Key facts
- Brand
- Toyo
- Model
- TOYO-F40
- Category
- Other Electronics
- Industry
- Industrial
- Documents
- 2
- Languages
- ZH · EN
- Last added
- 2026-11-17
Start here

TOYO TOYO-F40 Digital Multifunction Protection Relay Operation Manual
This operation manual covers the TOYO-F40 digital multifunction protection relay, a microprocessor-based device with a withdrawable case and RS-485 interface. It shows phase voltage, current, phase angle, power, and energy, and supports definite-time and inverse-time protection curves.
The relay stores up to 1024 event records and six waveform records, with a CB trip counter up to 65,535. A 4x20 LCD and front-panel keys provide access to measurement, status, record, system information, protection setting, CB control, contact planning, date/time, and communication menus. This manual is written in Chinese.
TOYO-F40 specifications
| Model | TOYO-F40 |
|---|---|
| Working power supply | AC/DC 80~260V |
| Event record capacity | 1024 entries |
| Waveform record capacity | 6 records |
| Waveform record length | 168 cycle fixed |
| CB trip counter maximum | 65535 |
| Display | 4x20 LCD |
| Communication interface | RS-485 |
Source: TOYO TOYO-F40 Digital Multifunction Protection Relay Operation Manual
All TOYO-F40 documents by type
Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.
Ratings, dimensions and ordering codes, for selection and design work.
Questions answered in these manuals
What protection curves does the TOYO-F40 support?
It supports definite-time and inverse-time curves, including normal, very, and extremely inverse types.
From: TOYO TOYO-F40 Digital Multifunction Protection Relay Operation Manual
How many event records can the TOYO-F40 store?
It can store up to 1024 event records, including pickup, trip, reset, setting change, and power on/off information.
From: TOYO TOYO-F40 Digital Multifunction Protection Relay Operation Manual
What are the possible exception response codes?
Exception responses include illegal function (01), illegal register address (02), illegal data value (03), slave device failure (04), acknowledge long duration command (05), busy servicing another long duration command (06), negative acknowledge (07), and invalid report index (08).
What is the valid range for the device ID on the Modbus network?
The device ID can range from 1 to 254.