Toyo DL-1-110 Heavy Duty Submersible Pump Installation, Operation & Maintenance Manual

Toyo DL-1-110 heavy duty submersible pump installation, operation and maintenance instructions covering inspection, lubrication, Megger testing…


Toyo DL-1-110 Heavy Duty Submersible Pump Installation, Operation & Maintenance Manual - cover page
Brand
Toyo
Category
Other
Document type
User Manual
Language
English
Pages
12
File format
PDF
File size
294 KB
Published
10 November, 2026
Updated
10 November, 2026
MD5 checksum
19D4464BF885900935C94112E1A85166

About this manual

The Toyo DL-1-110 is a heavy duty, portable, electrically powered submersible pump intended for removing water from enclosed sumps, irrigation areas and general dewatering chores. The pump has an oil-filled chamber between the pump section and the electric motor section with a sealing system that prevents water from entering the motor, and an induction-type motor with built-in overload protection. The manual states that the pump is not explosion-proof or spark-proof and must not be operated where flammable or explosive gases, vapors, liquids or particles are present.

These installation, operation and maintenance instructions cover unpacking and inspection, installation and operation, after-operation checks, regular inspection of lubricant and electrical insulation, troubleshooting, and a parts list for the DL1-110. The text includes the lubricant check procedure, a 500 VDC Megger test procedure, recommended inspection and replacement intervals, and a troubleshooting table with possible causes and corrections.

What's inside

  • Introduction
  • Unpacking and Inspection
  • Inspection of Pump
  • Installation and Operation
  • After Operation
  • Lubricant Check
  • Electrical Check (Megger Test)
  • Troubleshooting
  • Parts List

Specifications

ModelDL-1-110
Motor typeInduction-type motor with built-in overload protection
Power sourceSingle phase
LubricantTurbine Oil ISO VG #32
Lubricant inspection cycleEvery 1,000 hours of running time
Lubricant replacement cycleEvery 2,000 hours of running time
Insulation tester500 VDC Megger Tester
Power cable length32 ft
Discharge hose couplingNPT 2" (45 deg.) (STD.)

Frequently asked questions

What should be checked before operating the pump?

Check the nameplate information and inspect the pump for shipping damage; also verify that the power circuit and grounding are adequate.

How often should the lubricant in the oil chamber be checked?

Inspect the lubricant every 1,000 hours of running time and replace it every 2,000 hours; Toyo also recommends inspection once a year.

What lubricant should be used in the DL-1-110?

Turbine Oil ISO VG #32 is recommended; equivalent ISO VG #32 oils or 10W-30/40 engine oil can be used if turbine oil is difficult to obtain.

What does a Megger test reading below one meg-ohm mean?

It indicates damage to the cabtyre cable and/or the motor.

Download PDF (294 KB)