TOYO F40 Modbus Protocol and Memory Map Datasheet

Technical datasheet detailing the Modbus RTU register map, communication configuration, and data formats for TOYO F40 series protection relays.


TOYO F40 Modbus Protocol and Memory Map Datasheet - cover page
Brand
Toyo
Category
Other Electronics
Document type
Datasheet
Language
English
Pages
18
File format
PDF
File size
788 KB
Published
24 October, 2026
Updated
24 October, 2026
MD5 checksum
FB815BE123B57574FE22AFB902061FDB

About this manual

This document describes the Modbus RTU register map applicable to TOYO F40 series devices, including OCR, OCGR, OVR, UVR, OVGR, SGR, and NSOVR models. It outlines supported Modbus functions such as reading holding registers for set-points and dynamic values, forcing coils, and presetting multiple registers.

What's inside

  • Scope
  • Register Types
  • Functions and message parsing
  • Exception Responses
  • Data Formats
  • Communication Configuration
  • Register Map

Specifications

Applicable ModelsOCR/OCGR/OVR/UVR/OVGR/SGR/NSOVR
Device ID Range1 - 254
Data Bit8 bit
Stop Bit1 bit
Parity BitNone(0)
Supported Baud Rates (RS-485)300, 600, 1200, 2400, 4800, 9600, 19200
Supported Baud Rates (RS-232)19200

Frequently asked questions

What are the possible exception response codes?

Exception responses include illegal function (01), illegal register address (02), illegal data value (03), slave device failure (04), acknowledge long duration command (05), busy servicing another long duration command (06), negative acknowledge (07), and invalid report index (08).

What is the valid range for the device ID on the Modbus network?

The device ID can range from 1 to 254.

What are the supported baud rates for the RS-485 interface?

The supported baud rates are 300, 600, 1200, 2400, 4800, 9600, and 19200.

What is the maximum value for Phase A Voltage Magnitude?

The maximum value for Phase A Voltage Magnitude is 1,625,000.00 V.