Technical datasheet detailing the Modbus RTU register map, communication configuration, and data formats for TOYO F40 series protection relays.
This document describes the Modbus RTU register map applicable to TOYO F40 series devices, including OCR, OCGR, OVR, UVR, OVGR, SGR, and NSOVR models. It outlines supported Modbus functions such as reading holding registers for set-points and dynamic values, forcing coils, and presetting multiple registers.
| Applicable Models | OCR/OCGR/OVR/UVR/OVGR/SGR/NSOVR |
|---|---|
| Device ID Range | 1 - 254 |
| Data Bit | 8 bit |
| Stop Bit | 1 bit |
| Parity Bit | None(0) |
| Supported Baud Rates (RS-485) | 300, 600, 1200, 2400, 4800, 9600, 19200 |
| Supported Baud Rates (RS-232) | 19200 |
Exception responses include illegal function (01), illegal register address (02), illegal data value (03), slave device failure (04), acknowledge long duration command (05), busy servicing another long duration command (06), negative acknowledge (07), and invalid report index (08).
The device ID can range from 1 to 254.
The supported baud rates are 300, 600, 1200, 2400, 4800, 9600, and 19200.
The maximum value for Phase A Voltage Magnitude is 1,625,000.00 V.