Safety and installation instructions for the TDK-Lambda HFE2500-S1U power supply rack, covering grounding, environmental conditions, and hazard warnings.
This document provides safety instructions and operational guidelines for the TDK-Lambda HFE2500-S1U power supply rack. It details requirements for installation in restricted access areas, proper grounding procedures for Class I products, and precautions regarding live circuits to prevent electrical shock.
The manual specifies environmental conditions such as an ambient temperature range of -10°C to 70°C (with derating) and a maximum altitude of 3000m. It also outlines energy hazards associated with the output bus bars and provides recommendations for AC power cables, noting that no internal fuses are present.
| Overvoltage Category | Category II |
|---|---|
| Pollution Degree | 2 |
| Max Operational Altitude | 3000m above sea level |
| Ambient Temperature (100% load) | -10°C-50°C |
| Max Ambient Temperature (with derating) | 70°C |
| Protection Class | Class I |
| AC Input Voltage Rating | 100-240V~, 50/60Hz |
| Branch Circuit Overcurrent Protection | 30A max. |
No, it is not authorized without express written approval from the managing director of TDK-Lambda.
No, internal adjustment or component replacement is only allowed by authorized TDK Lambda qualified service personnel.
No, there are no fuses in the unit; a 30A max. overcurrent protective device must be incorporated in the building wiring.