Instruction manual for the SMC EX510-TF2Z170EN fieldbus gateway unit for EtherNet/IP, covering specifications, wiring, settings, and maintenance.
This instruction manual covers the SMC EX510-TF2Z170EN fieldbus gateway unit for EtherNet/IP. The unit is intended to control pneumatic valves and I/O while connected to the EtherNet/IP protocol.
The document includes safety instructions, general and gateway specifications, part names, DIN rail installation, communication and power supply wiring, branch cable connections, IP address and communication switch settings, LED display indications, maintenance, and disposal guidance.
| Rated voltage | 24 VDC |
|---|---|
| Enclosure rating | IP20 |
| Withstand voltage | 500 VAC for 1 minute (between FG and terminal block) |
| Insulation resistance | 10 MΩ or more 500 VDC (between FG and terminal block) |
| Operating ambient temperature | -10 to +50 °C |
| Storage ambient temperature | -20 to +60 °C |
| Ambient humidity | 35 to 85% RH (no condensation) |
| Gateway control power supply | 24 VDC ±10% |
| Output power supply | 24 VDC +10% / -5% |
| Rated current for GW control | 200 mA max. |
| Rated current for outputs | 3.6 A max. |
| Number of outputs | 64 |
| Weight | 400 g (including accessories) |
| Communication speed | 10 / 100 Mbps (auto selection or manual setting) |
| Communication method | Full duplex/Half duplex (auto selection or manual setting) |
| Fieldbus protocol | EtherNet/IP (conformance version: composite 9) |
| I/O message input | 16 bytes (assembly instance: 100) |
| I/O message output | 16 bytes (assembly instance: 150) |
| IP address range | 192.168.0.1 to 192.168.0.254 or 192.168.1.1 to 192.168.1.254 |
| Number of branches | Input: 4 branches / Output: 4 branches |
| Communication speed for branches | 750 kbps |
| Output branch current | Max. 1.5 A per branch |
| Branch cable length | 20 m max. |
| DIN rail mounting tightening torque | 0.6 N•m |
| Power supply connector tightening torque | 0.5 to 0.6 N•m |
| Ground resistance | 100 Ω or less |
It is intended to control pneumatic valves and I/O while connected to the EtherNet/IP protocol.
It is mounted on a DIN rail using the mounting bracket, and the mounting bracket screw is tightened to 0.6 N•m.
The IP address is set with the SW2 and SW1 switches, or the unit can obtain an address from a DHCP server in DHCP mode.
It sets the output status when the fieldbus has a communication error or is in an idle state: CLEAR clears the output and HOLD holds it.
Turn off the power supply, cut off the supply pressure, confirm that air is released to atmosphere, and have maintenance performed only by qualified personnel.