SMC EX510-TF2Z170EN Fieldbus Gateway Unit for EtherNet/IP Instruction Manual

Instruction manual for the SMC EX510-TF2Z170EN fieldbus gateway unit for EtherNet/IP, covering specifications, wiring, settings, and maintenance.


SMC EX510-TF2Z170EN Fieldbus Gateway Unit for EtherNet/IP Instruction Manual - cover page
Brand
SMC
Category
Other Electronics
Document type
User Manual
Language
English
Pages
2
File format
PDF
File size
1.1 MB
Published
17 November, 2026
Updated
17 November, 2026
MD5 checksum
9F2CA159BC6C37D17FC86EB6E0B92339

About this manual

This instruction manual covers the SMC EX510-TF2Z170EN fieldbus gateway unit for EtherNet/IP. The unit is intended to control pneumatic valves and I/O while connected to the EtherNet/IP protocol.

The document includes safety instructions, general and gateway specifications, part names, DIN rail installation, communication and power supply wiring, branch cable connections, IP address and communication switch settings, LED display indications, maintenance, and disposal guidance.

What's inside

  • Safety Instructions
  • Specifications
  • Name and Function of Parts
  • Installation
  • Wiring
  • Setting
  • How to Order
  • Outline Dimensions
  • LED Display
  • Maintenance

Specifications

Rated voltage24 VDC
Enclosure ratingIP20
Withstand voltage500 VAC for 1 minute (between FG and terminal block)
Insulation resistance10 MΩ or more 500 VDC (between FG and terminal block)
Operating ambient temperature-10 to +50 °C
Storage ambient temperature-20 to +60 °C
Ambient humidity35 to 85% RH (no condensation)
Gateway control power supply24 VDC ±10%
Output power supply24 VDC +10% / -5%
Rated current for GW control200 mA max.
Rated current for outputs3.6 A max.
Number of outputs64
Weight400 g (including accessories)
Communication speed10 / 100 Mbps (auto selection or manual setting)
Communication methodFull duplex/Half duplex (auto selection or manual setting)
Fieldbus protocolEtherNet/IP (conformance version: composite 9)
I/O message input16 bytes (assembly instance: 100)
I/O message output16 bytes (assembly instance: 150)
IP address range192.168.0.1 to 192.168.0.254 or 192.168.1.1 to 192.168.1.254
Number of branchesInput: 4 branches / Output: 4 branches
Communication speed for branches750 kbps
Output branch currentMax. 1.5 A per branch
Branch cable length20 m max.
DIN rail mounting tightening torque0.6 N•m
Power supply connector tightening torque0.5 to 0.6 N•m
Ground resistance100 Ω or less

Frequently asked questions

What is the intended use of the EX510-TF2Z170EN gateway unit?

It is intended to control pneumatic valves and I/O while connected to the EtherNet/IP protocol.

How is the gateway unit mounted?

It is mounted on a DIN rail using the mounting bracket, and the mounting bracket screw is tightened to 0.6 N•m.

How can the IP address be set?

The IP address is set with the SW2 and SW1 switches, or the unit can obtain an address from a DHCP server in DHCP mode.

What does the HOLD/CLEAR setting control?

It sets the output status when the fieldbus has a communication error or is in an idle state: CLEAR clears the output and HOLD holds it.

What maintenance precautions are required?

Turn off the power supply, cut off the supply pressure, confirm that air is released to atmosphere, and have maintenance performed only by qualified personnel.