Simplex 4100 Series graphic annunciator LED/switch and 24 point I/O modules: features, model selection tables, wiring and specifications.
This data sheet (S4100-0005 Rev. 9 3/2019) describes the Simplex 4100 Series Graphic Annunciator Modules, which provide LED and switch control for custom graphic annunciator panels. It covers the 4100-7401 24 Point I/O Graphic Module, the 4100-7402 64/64 LED Switch Controller, the 4100-7403 32 Point LED Driver Module and the 4100-7404 32 Point Switch Input Module, all intended for use with Simplex 4007ES, 4010ES, 4100ES and 4100U series fire alarm control units, and also compatible with legacy 4100, 4120 and 4020 series panels (with a 4020 note for the 4100-7401).
The document lists module functions, mounting plates and cabinets, product selection tables, cabinet dimensions and a specifications table covering voltage, current, RUI communications capacity, wiring, temperature and humidity. It also includes a mounting reference figure and cabinet reference drawings, and notes listings under UL, ULC, CSFM and MEA (NYC).
| Operating voltage | 18.9 to 32 VDC; 24 VDC nominal from the fire alarm control unit |
|---|---|
| Operating temperature | 32° F to 120° F (0° C to 49° C) |
| Operating humidity | Up to 93% RH, non-condensing at 90° F (32° C) maximum |
| 4100-7401 points | 24 points, each selectable as a switch input or a lamp/relay driver output |
| 4100-7401 driver rating | 150 mA @ 24 VDC per point, inrush current limited |
| 4100-7402 capacity | Up to 64 switches and 64 LEDs, with 32 on-board LED drivers |
| RUI device capacity | 4100ES and 4100U: up to 31 total remote RUI devices |
| Communications wiring | Single, twisted wire pair (some applications may require shields), 18 AWG |
| Cabinet sizes | 2-Unit, 4-Unit and 6-Unit cabinets |
They are for use with Simplex 4007ES, 4010ES, 4100ES and 4100U series fire alarm control units, and are also compatible with legacy 4100, 4120 and 4020 series panels.
A 4100ES or 4100U control unit supports up to 31 total remote RUI devices.
No, the document states that the 4100-7401 is not compatible with installed Simplex 4020 Series fire alarm control panels.
Mounting is on dedicated mounting plates, with up to 3 modules per plate.