This document is an operator manual for the Simplex 4100 Fire Indicator Panel
This manual provides step-by-step instructions for operating the Simplex 4100 Fire Indicator Panel, including handling alarm and fault conditions, system reset, point control, and maintenance procedures. It details compatible detectors and batteries, system specifications, and test protocols required by Australian standards. The guide also covers advanced functions, display operations, and troubleshooting steps for system malfunctions.
| System Capacity | 1,000 points of addressable input/output devices or conventional zones |
|---|---|
| Cabinet Size | Dependent on system configuration |
| Mains Input | 240V AC, +6%,-10%, 50Hz |
| Internal Power Supply | 24V DC @ 6.5A |
| Standby Battery | 24V sealed lead acid up 110Ah |
| Temperature Range | -5 C to 45 C |
| Humidity | 10% to 90% RH non-condensing |
Operate the "Alarm Test" switch to automatically test all detector zones and indicate correct operation by illuminating each zone LED, then reset.
Call your local Simplex branch office listed in the Yellow Pages for all malfunctions, or request a qualified Simplex technician for installation, testing, and troubleshooting.
Compatible batteries include Power-Sonic PS12 series, Sonnenschien A200 series, Sonnenschien A300 series, and Yuasa NP series.