This manual provides installation, operation, and maintenance instructions for SST and SRS Day Tanks, and includes a troubleshooting guide.
The document serves as a comprehensive guide for the Simplex SST and SRS day tank system. It details critical safety requirements regarding location, such as proximity to engines and flash point restrictions for combustible liquids (NFPA 321). The manual provides step-by-step instructions for installation, including plumbing connections using black iron or copper tubing, venting configurations, and electrical grounding procedures.
| Maximum Flash Point Temperature | 100°F |
|---|---|
| Electrical Supply Voltage | 115-1-60 |
| Maximum Withstand Pressure (10 and 25 gallon) | 25PSI |
| Maximum Withstand Pressure (50–400 gallon) | 15PSI |
The system must only be used with combustible liquids having a flash point at or above 100°F (Class II or Class III).
All plumbing to and from the Day Tank should be black iron pipe or copper tubing.
No, valves must not be installed in the vent line as it provides necessary pressure relief.