Siemens QVE1901 Flow Switch Installation Guide

Siemens QVE1901 flow switch for liquids in piping DN 20 to 200: switching values, installation, electrical connection, adjustment and technical data.


Siemens QVE1901 Flow Switch Installation Guide - cover page
Brand
Siemens
Category
flow transmitter
Document type
Installation Guide
Language
English
Pages
7
File format
PDF
File size
246 KB
Published
17 November, 2026
Updated
17 November, 2026
Model
QVE1901
MD5 checksum
984FB15500DD13E1FAAAB9256CC018C0

About this manual

This document describes the Siemens QVE1901 flow switch for liquids in piping DN 20…200. It covers the mode of operation, the mechanical design with a paddle system, permanent magnet and reed contact, the ordering information (Flow switch QVE1901, 1592P01), engineering notes and the switching value table for water at 20 °C.

Installation and electrical connection are explained step by step, including the required smoothing sections, the upright installation position, the G¾ brass connecting nut tightening torque, and wiring through the EN 175301-803-A junction box. A section on adjusting the switching unit describes how the make (NO) and break (NC) contact types are set, followed by technical data, dimensions and notes on maintenance, decommissioning and disposal.

What's inside

  • Mode of operation
  • Ordering
  • Mechanical design
  • Engineering notes
  • Flow switch installation
  • Installation notes
  • Electrical connections
  • Adjust switching unit
  • Technical data
  • Dimensions

Specifications

Field of useWater and antifreeze solutions (not suitable for ammonia)
Piping diameterDN 20…200
Type of switchReed contact
Contact ratingAC 230 V, 1 A / DC 48 V, 1 A
Max. switching capacityAC 26 VA / DC 20 W
Medium temperature-20…110 °C
Nominal pressurePN 25
Housing protectionIP 65 per EN 60 529
Operation and storage temperature-20…80 °C
Weight0.31 kg excluding packaging
Housing materialPolyamide, black

Frequently asked questions

What media can the QVE1901 flow switch be used with?

It is suitable for water and antifreeze solutions, but not for ammonia. The medium must not freeze.

What is the maximum switching capacity of the flow switch?

The maximum switching capacity is AC 26 VA or DC 20 W, with a contact rating of AC 230 V, 1 A or DC 48 V, 1 A.

How do I set the contact type to normally open or normally closed?

The switching unit is set by hand: the make contact (normally open) is marked with a RED arrow and the break contact (normally closed) with a WHITE arrow.

Does the flow switch need maintenance?

No. The flow switch is maintenance-free and cannot be repaired by the user; a defective device must be returned to the manufacturer.

Download PDF (246 KB)