Siemens data sheet for QBE2003-P and QBE2103-P pressure sensors, covering models, ordering, accessories, working principle and technical data for HVAC use.
This Siemens product data sheet covers the QBE2003-P and QBE2103-P pressure sensor series. The sensors are intended for measuring relative pressure in HVAC applications, including hydraulic and pneumatic systems for neutral or slightly corrosive liquid and gas (steam) media. The document lists model numbers, pressure ranges, output signals, ordering information and accessories.
It explains the piezoresistive measuring principle and the ceramic diaphragm in direct contact with the medium. It also describes the mechanical design, installation notes, disposal instructions, technical data, internal wiring for QBE2003 and QBE2103 models, and dimensions. This manual is written in Chinese.
| Pressure range | Relative pressure 0 - 60 bar |
|---|---|
| Supply voltage (QBE2003) | AC 24 V ±15 %, 50...60 Hz or DC 12...33 V |
| Supply voltage (QBE2103) | DC 7…33 V |
| Output signal (QBE2003) | DC 0...10 V |
| Output signal (QBE2103) | DC 4…20 mA |
| Response time | <2 ms, typical 1 ms |
| Medium temperature | -15... +125 °C |
| Protection standard | IP 65, EN 60529 |
| Pressure connection | External thread G ½ in, internal thread M5 |
| Weight | 0.171 kg including packaging |
The sensors measure relative pressure in HVAC applications.
The QBE2003-P models provide a DC 0...10 V output signal.
The document states a relative pressure measuring range of 0 to 60 bar.
The sensor has protection standard IP 65 according to EN 60529.