Technical datasheet for the Schneider Electric Compact NSX630N Micrologic 2.3 circuit breaker, detailing ratings, breaking capacities, and trip unit…
This document is a technical datasheet for the Schneider Electric Compact NSX630N circuit breaker equipped with the Micrologic 2.3 electronic trip unit. It is designed for distribution applications in AC networks with a frequency of 50/60 Hz and a rated current of 630 A. This manual is written in Chinese.
| Rated current | 630 A ( 40 °C ) |
|---|---|
| Rated insulation voltage | 800 V AC 50/60 Hz |
| Rated impulse withstand voltage | 8 kV |
| Rated operational voltage | 690 V AC 50/60 Hz |
| Breaking capacity (600 V) | 20 kA |
| Breaking capacity (480 V) | 50 kA |
| Breaking capacity (240 V) | 85 kA |
| Trip unit name | Micrologic 2.3 |
| Pollution degree | 3 |
| Height | 255 mm |
| Product weight | 6.2 kg |
| Ambient air temperature for operation | -35...70 °C |
The rated current is 630 A at 40 °C.
Yes, it is suitable for isolation conforming to EN 60947 -2 and IEC 60947 -2.