Pepperl+Fuchs KFA5-SR2-Ex1.W Switch Amplifier Datasheet

The Pepperl+Fuchs KFA5-SR2-Ex1.W is a 1-channel isolated barrier switch amplifier for intrinsic safety, with NAMUR/contact inputs and a relay output.


Pepperl+Fuchs KFA5-SR2-Ex1.W Switch Amplifier Datasheet - cover page
Brand
pepperl+Fuchs
Category
electronic components
Document type
Datasheet
Language
English
Pages
6
File format
PDF
File size
1.2 MB
Published
23 November, 2026
Updated
23 November, 2026
MD5 checksum
E16A35D042F0B9CAE83A9210526C98C6

About this manual

The Pepperl+Fuchs KFA5-SR2-Ex1.W is a 1-channel isolated barrier switch amplifier used for intrinsic safety applications. It transfers digital signals from NAMUR sensors or mechanical contacts in a hazardous area to a safe area, where a proximity sensor or switch controls a form C changeover relay contact for the safe area load.

The unit is supplied with 103.5 ... 126 V AC at 45 ... 65 Hz on terminals 14 and 15 and consumes 1 W. It is rated SIL 2 and provides reinforced galvanic isolation between input, output and power supply. Hazardous-area markings include [Ex ia Ga] IIC, [Ex ia Da] IIIC and [Ex ia Ma] I, and LEDs indicate power, relay output and line-fault status according to NAMUR NE44.

What's inside

  • Function
  • Connection
  • Technical Data
  • Indicators/settings
  • Directive conformity
  • Ambient conditions
  • Mechanical specifications
  • International approvals
  • Assembly
  • Accessories

Specifications

Supply voltage103.5 ... 126 V AC, 45 ... 65 Hz
Power consumption1 W
Safety integrity levelSIL 2
Input signal typeDigital
Output contact loading253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Galvanic isolationReinforced insulation, 300 Veff (input/output, input/power supply, output/power supply)
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Massapprox. 150 g
Degree of protectionIP20

Frequently asked questions

What supply voltage does the KFA5-SR2-Ex1.W use?

It uses 103.5 ... 126 V AC at 45 ... 65 Hz on connection terminals 14 and 15.

What safety integrity level is the KFA5-SR2-Ex1.W rated for?

It is rated SIL 2 according to IEC/EN 61508 and IEC/EN 61511.

Can line fault detection be turned off?

Yes. Switch S3 enables or disables line fault detection of the field circuit.

What happens during an error condition?

The relays revert to their de-energized state and the LEDs indicate the fault according to NAMUR NE44.