This document provides an introduction to the KFD*-HM*-16 HART Multiplexer System, including the product's features and installation and usage instructions.
This manual describes the HART multiplexer system KFD*-HM*-16, consisting of the HART multiplexer master KFD2-HMM-16 and HART multiplexer slaves KFD0-HMS-16. It covers product specifications, system structure, mounting and installation, commissioning, configuration with PACTware, operation, diagnosis, and maintenance.
The system is used to establish a HART connection to analog field devices while maintaining conventional 4 mA to 20 mA circuits. The devices can be used in Zone 2 or in non-hazardous areas, are supplied with 24 VDC, and connect to a maintenance station or process control system via an RS-485 interface.
| Maximum field devices per multiplexer slave | 16 analog field devices |
|---|---|
| Maximum field devices per system | 256 analog field devices |
| Maximum additional multiplexer slaves | 15 |
| Supply voltage | 24 VDC |
| Communication interface | RS-485 |
| Transfer rate | max. 57600 baud |
| Galvanic isolation | Supply, analog signals, and RS-485 interface isolated from each other |
| HART signal frequencies | 1200 Hz and 2200 Hz |
| Slave address range | 1 to 15 |
The system consists of one HART multiplexer master KFD2-HMM-16 and several HART multiplexer slaves KFD0-HMS-16.
A maximum of 256 analog field devices can be connected to the HART multiplexer system.
The devices are supplied with 24 VDC.
The device is connected to a maintenance station via an RS-485 interface.