User manual for nVent RAYCHEM ECW-GF electronic controller with ground-fault protection for temperature control applications.
The nVent RAYCHEM ECW-GF is a digital electronic controller designed for precise temperature control in applications like pipe freeze protection, floor heating, and snow melting. It features integrated 30-mA ground-fault protection and a NEMA 4X enclosure for wall or pipe mounting. The controller includes a digital display and status LEDs to show set point, actual temperature, and alarm conditions. It can be programmed via front panel buttons to set temperature, deadband, and alarm thresholds. An optional remote display panel (ECW-GF-DP) offers remote alarm indication and ground-fault testing. The unit operates on 100–277 V, supports up to 30 A, and maintains temperatures up to 200°F (93°C).
| Voltage Range | 100 to 277 V |
|---|---|
| Maximum Switching Current | 30 amperes |
| Temperature Control Range | 32°F to 200°F (0°C to 93°C) |
| Ground-Fault Protection | 30 mA fixed |
| Enclosure Rating | NEMA 4X |
| Display Type | Digital display |
| Alarm Relay Type | Form C |
| Thermistor Included | 25-foot thermistor |
The ECW-GF can be programmed to maintain temperatures up to 200°F (93°C).
The ECW-GF supports voltages from 100 to 277 V.
The ECW-GF can be wall mounted or installed on a pipe using the optional Raychem FTC-PSK pipe stand kit.