Installation manual for nVent RAYCHEM RMM 3-4X and RMM 3-24VDC-4X remote monitoring modules, covering tools, approvals, components, specifications, mounting…
This installation manual is for the nVent RAYCHEM RMM 3-4X and RMM 3-24VDC-4X remote monitoring modules used with the nVent RAYCHEM control system. It lists required tools, approvals, supplied components and accessories, and technical specifications.
It also describes safe-use conditions, branch circuit protection, disconnect requirements, enclosure mounting, DIN rail attachment, and power and ground wiring connections.
| Supply voltage (RMM 3-4X) | 115/230 Vac, jumper selectable, 50/60 Hz |
|---|---|
| Supply voltage (RMM 3-24VDC-4X) | 24 Vdc nominal, min 10 Vdc, max 30 Vdc |
| Power consumption | 2.5 VA |
| Ambient operating range | -40 C to +60 C |
| Relative humidity | 5 to 95%, noncondensing |
| Altitude | Up to 2000 m |
| Environment | Pollution Degree 2, Overvoltage Category II |
| Protection | Type 4X or better enclosure when installed outdoors |
| Temperature sensors | 3-wire RTD (Pt 100) |
| Temperature coefficient | Per IEC 751-1983 (100 ohm at 0 C) |
| Sensor connections | Can be extended with a 3-core shielded cable of 20 ohm max. per conductor, advised maximum length 150 m |
| Sensor input wire connections | 3 x 1.5 mm2 cable |
| RS-485 connections | Shielded, single twisted pair, max. 1200 m |
| Temperature measurement range | -100 C to +700 C |
| Replaceable fuse (RMM 3) | F 50 mA/250 V, Littlefuse Series 372 TR5 50 mA, part number 37200500001 |
| Replaceable fuse (RMM 3-24VDC) | F 200 mA/250 V, Wickmann part number 19370-034-K (FAST BLOW) |
A 3/8 hex key is required for the RMM 3-4X enclosure.
It uses 3-wire RTD (Pt 100) temperature sensors.
The temperature measurement range is -100 C to +700 C.
The RMM 3-4X must be protected by a branch circuit breaker rated no more than 20 A.