nVent RAYCHEM RMM 3-4X / RMM 3-24VDC-4X Remote Monitoring Module Installation Manual

Installation manual for nVent RAYCHEM RMM 3-4X and RMM 3-24VDC-4X remote monitoring modules, covering tools, approvals, components, specifications, mounting…


nVent RAYCHEM RMM 3-4X / RMM 3-24VDC-4X Remote Monitoring Module Installation Manual - cover page
Brand
nVent RAYCHEM
Category
Monitoring Equipment
Document type
Installation Guide
Language
English
Pages
8
File format
PDF
File size
1.6 MB
Published
16 November, 2026
Updated
16 November, 2026
MD5 checksum
2D8A53C58314C4D8CFF2533E6FE74BD5

About this manual

This installation manual is for the nVent RAYCHEM RMM 3-4X and RMM 3-24VDC-4X remote monitoring modules used with the nVent RAYCHEM control system. It lists required tools, approvals, supplied components and accessories, and technical specifications.

It also describes safe-use conditions, branch circuit protection, disconnect requirements, enclosure mounting, DIN rail attachment, and power and ground wiring connections.

What's inside

  • Tools required
  • Approvals
  • Monitoring system components and accessories
  • RMM 3 specification
  • Conditions of safe use
  • Branch circuit protection
  • Disconnect device
  • Mounting in enclosure
  • Attaching to DIN rail
  • Power and ground wiring

Specifications

Supply voltage (RMM 3-4X)115/230 Vac, jumper selectable, 50/60 Hz
Supply voltage (RMM 3-24VDC-4X)24 Vdc nominal, min 10 Vdc, max 30 Vdc
Power consumption2.5 VA
Ambient operating range-40 C to +60 C
Relative humidity5 to 95%, noncondensing
AltitudeUp to 2000 m
EnvironmentPollution Degree 2, Overvoltage Category II
ProtectionType 4X or better enclosure when installed outdoors
Temperature sensors3-wire RTD (Pt 100)
Temperature coefficientPer IEC 751-1983 (100 ohm at 0 C)
Sensor connectionsCan be extended with a 3-core shielded cable of 20 ohm max. per conductor, advised maximum length 150 m
Sensor input wire connections3 x 1.5 mm2 cable
RS-485 connectionsShielded, single twisted pair, max. 1200 m
Temperature measurement range-100 C to +700 C
Replaceable fuse (RMM 3)F 50 mA/250 V, Littlefuse Series 372 TR5 50 mA, part number 37200500001
Replaceable fuse (RMM 3-24VDC)F 200 mA/250 V, Wickmann part number 19370-034-K (FAST BLOW)

Frequently asked questions

What tools are required to install the RMM 3-4X enclosure?

A 3/8 hex key is required for the RMM 3-4X enclosure.

What temperature sensors does the module use?

It uses 3-wire RTD (Pt 100) temperature sensors.

What is the temperature measurement range?

The temperature measurement range is -100 C to +700 C.

What branch circuit protection is required for AC versions?

The RMM 3-4X must be protected by a branch circuit breaker rated no more than 20 A.