nVent RAYCHEM industrial heat-tracing systems must be installed correctly to ensure proper operation and to prevent shock and fire. This manual provides important safety safeguards and warnings, as well as detailed installation instructions.
This manual covers the installation and maintenance of nVent RAYCHEM Series Resistance (SC) heat-tracing systems, which provide electrical freeze protection and temperature maintenance for long pipelines on thermally insulated metal and plastic pipes. It is written for use together with the nVent design documentation for each project and the SC, SC/H, SC/F data sheets (H57027, H57961) and components and accessories data sheets (H57780, H57943A).
The document begins with important safeguards covering fire and shock hazards, ground-fault protection requirements, and hazardous-location precautions. It then walks through cable verification and selection, installation directly on pipes or in channel, component installation, control and monitoring, thermal insulation and marking, power supply and electrical protection, commissioning, test procedures (including insulation resistance, continuity, capacitance and power checks), a troubleshooting guide, and installation and inspection records. The text is presented in English, Portuguese, and Spanish.
| Cable configurations | Single, dual, or triple conductor |
|---|---|
| Minimum installation temperature | -40°F (-40°C) |
| Minimum bend radius | 1 inch |
| Cable tag attachment distance | Within 3 inches (75 mm) of the power connection |
| Extended warranty | 10-year warranty with online registration within 30 days |
Sections 427 (pipelines and vessels) and 500 (classified locations) of the National Electrical Code (NEC), and Part 1 of the Canadian Electrical Code, Sections 18 and 62, govern the installation, along with any other applicable national or local codes.
Yes, ground-fault equipment protection must be used on each heating cable branch circuit to minimize the danger of fire from sustained electrical arcing if the cable is damaged or improperly installed.
No. Approvals and performance of the heat-tracing systems are based on the use of approved components and accessories, and substitute parts must not be used.
The circuit identification tag must be permanently attached within 3 inches (75 mm) of the power connection.