nVent RAYCHEM E507S-LS Line-Sensing Thermostat Datasheet

nVent RAYCHEM E507S-LS line-sensing thermostat for hazardous locations: set point range, electrical rating, sensor and approvals.


nVent RAYCHEM E507S-LS Line-Sensing Thermostat Datasheet - cover page
Brand
nVent RAYCHEM
Category
Other
Document type
Datasheet
Language
English
Pages
2
File format
PDF
File size
284 KB
Published
10 November, 2026
Updated
10 November, 2026
MD5 checksum
17257EAA351DFA88F564996FA4C13DE2

About this manual

This two-page datasheet presents the nVent RAYCHEM E507S-LS line-sensing thermostat, a device designed for controlling heat-tracing systems in hazardous locations. According to the document, the E507S-LS senses pipe or tank wall temperatures and can control a single heat-tracing circuit or act as a pilot control of a contactor switching multiple heat-tracing circuits. It can also be used to indicate low-temperature or high-temperature alarm conditions.

The datasheet lists the product specifications, including the lacquer-coated cast-aluminum enclosure, the 25°F to 325 °F set point range, a SPDT switch rated 22 A at 125 / 250 / 480 Vac, a fluid-filled silicone bulb sensor with 9 ft capillary, and screw terminals for 10–14 AWG wire. It also lists hazardous-location approvals for Class I, Class II and Class III divisions and groups, plus outline dimensions and the adjusting knob and terminal block layout.

What's inside

  • Product overview
  • Specifications
  • Enclosure
  • Entries
  • Set point range
  • Sensor exposure limits
  • Housing exposure limits
  • Switch and electrical rating
  • Sensor type and material
  • Connection terminals

Specifications

EnclosureTYPE 4, 7, 9, lacquer-coated cast-aluminum housing, stainless steel hardware
EntriesOne 3/4-in (19 mm) NPT conduit hub
Set point range25°F to 325°F (–4°C to 163°C)
Sensor exposure limits–40°F to 420°F (–40°C to 215°C)
Housing exposure limits–40°F to 140°F (–40°C to 60°C)
SwitchSPDT
Electrical rating22 A at 125 / 250 / 480 Vac
Accuracy±6°F (±3.3°C)
Deadband2°F to 12°F (1.1°C to 6.7°C) above actuation temperature
Setpoint repeatability±3°F (±1.7°C)
Sensor typeFluid-filled (silicone) bulb and 9 ft (2.7 m) capillary
Sensor material300 series stainless steel
Connection terminalsScrew terminals, 10–14 AWG (2–5 mm²)

Frequently asked questions

What is the set point range of the E507S-LS thermostat?

The set point range is 25°F to 325°F (–4°C to 163°C).

What is the electrical rating of the switch?

The SPDT switch is rated 22 A at 125 / 250 / 480 Vac.

What type of sensor does the thermostat use?

It uses a fluid-filled (silicone) bulb with a 9 ft (2.7 m) capillary, made of 300 series stainless steel.

What hazardous location approvals does the E507S-LS carry?

It is approved for Class I, Div. 1 and 2, Groups B, C, D; Class II, Div. 1 and 2, Groups E, F, G; and Class III hazardous locations.

Download PDF (284 KB)