nVent RAYCHEM E507S-LS line-sensing thermostat for hazardous locations: set point range, electrical rating, sensor and approvals.
This two-page datasheet presents the nVent RAYCHEM E507S-LS line-sensing thermostat, a device designed for controlling heat-tracing systems in hazardous locations. According to the document, the E507S-LS senses pipe or tank wall temperatures and can control a single heat-tracing circuit or act as a pilot control of a contactor switching multiple heat-tracing circuits. It can also be used to indicate low-temperature or high-temperature alarm conditions.
The datasheet lists the product specifications, including the lacquer-coated cast-aluminum enclosure, the 25°F to 325 °F set point range, a SPDT switch rated 22 A at 125 / 250 / 480 Vac, a fluid-filled silicone bulb sensor with 9 ft capillary, and screw terminals for 10–14 AWG wire. It also lists hazardous-location approvals for Class I, Class II and Class III divisions and groups, plus outline dimensions and the adjusting knob and terminal block layout.
| Enclosure | TYPE 4, 7, 9, lacquer-coated cast-aluminum housing, stainless steel hardware |
|---|---|
| Entries | One 3/4-in (19 mm) NPT conduit hub |
| Set point range | 25°F to 325°F (–4°C to 163°C) |
| Sensor exposure limits | –40°F to 420°F (–40°C to 215°C) |
| Housing exposure limits | –40°F to 140°F (–40°C to 60°C) |
| Switch | SPDT |
| Electrical rating | 22 A at 125 / 250 / 480 Vac |
| Accuracy | ±6°F (±3.3°C) |
| Deadband | 2°F to 12°F (1.1°C to 6.7°C) above actuation temperature |
| Setpoint repeatability | ±3°F (±1.7°C) |
| Sensor type | Fluid-filled (silicone) bulb and 9 ft (2.7 m) capillary |
| Sensor material | 300 series stainless steel |
| Connection terminals | Screw terminals, 10–14 AWG (2–5 mm²) |
The set point range is 25°F to 325°F (–4°C to 163°C).
The SPDT switch is rated 22 A at 125 / 250 / 480 Vac.
It uses a fluid-filled (silicone) bulb with a 9 ft (2.7 m) capillary, made of 300 series stainless steel.
It is approved for Class I, Div. 1 and 2, Groups B, C, D; Class II, Div. 1 and 2, Groups E, F, G; and Class III hazardous locations.