Instruction manual for the Mitsubishi FR-A500 transistorized inverter covering installation, wiring, operation, control parameters, protective functions…
This document serves as the instruction manual for the Mitsubishi FR-A500 transistorized inverter. It provides comprehensive handling information and precautions for the safe use of the equipment, including safety warnings regarding electric shock and fire prevention. The manual outlines the necessary steps to ensure the inverter is used to its optimum performance.
| Ambient temperature (Constant torque) | -10 °C to +50 °C |
|---|---|
| Ambient temperature (Variable torque) | -10 °C to +40 °C |
| Ambient humidity | 90%RH or less |
| Storage temperature | -20 °C to +65 °C |
| Maximum altitude | 1000m above sea level |
| Maximum vibration | 5.9 m/s 2 or less |
The inverter must be earthed (grounded) according to national and local safety regulations and electrical codes.
Power must be switched off and at least 10 minutes must wait to check for residual voltage.
The load used should be a three-phase induction motor only.
No, do not fit capacitive equipment such as a power factor correction capacitor to the inverter output side.