Installation manual for Mean Well MDR-10/20/40/60/100 DIN rail power supplies, covering mounting, wiring, warnings, and compliance declarations.
Mean Well MDR is a DIN rail power supply series with less than 1 W no-load power consumption, including models MDR-10, MDR-20, MDR-40, MDR-60, and MDR-100 with various output voltages and currents. The manual lists input and output ratings for each model and describes installation requirements such as ventilation clearances, wire selection, torque, fuses, and DIN rail mounting.
Additional sections cover electrical shock, burn, fire, and environmental warnings, including maximum operating temperatures and pollution degree 2 installation. The document also includes declarations of China RoHS, China VOC, and Five PBT TSCA conformity.
| Input voltage | 100-240 VAC |
|---|---|
| Input frequency | 50/60 Hz |
| No-load power consumption | <1 W |
| Ventilation clearance | 5 mm left/right, 40 mm above, 20 mm below |
| Wire temperature rating | At least 80°C |
| Wire strapping length | 6.5 mm (0.255 in) |
| Recommended screwdriver | 3 mm slotted |
| Terminal torque | 5.8 kgf-cm (5.0 Lb-in) |
| Maximum operating temperature (MDR-100-12) | 35°C |
| Maximum operating temperature (MDR-100-24/48) | 40°C |
| Maximum operating temperature (MDR-10/20/40/60 series) | 50°C |
| Pollution degree | 2 |
| Admissible DIN rail | TS35/7.5 or TS35/15 |
| Suggested fuse (MDR-10) | T2A/L250V |
| Suggested fuse (MDR-20) | T2A/L250V |
| Suggested fuse (MDR-40) | T2.5A/L250V |
| Suggested fuse (MDR-60) | T2.5A/L250V |
| Suggested fuse (MDR-100) | T4A/L250V |
| MDR-10-5 ratings | Input 100-240 VAC, 0.33 A, 50/60 Hz; output 5 V, 2 A |
| MDR-10-12 ratings | Input 100-240 VAC, 0.33 A, 50/60 Hz; output 12 V, 0.84 A |
| MDR-10-15 ratings | Input 100-240 VAC, 0.33 A, 50/60 Hz; output 15 V, 0.67 A |
| MDR-10-24 ratings | Input 100-240 VAC, 0.33 A, 50/60 Hz; output 24 V, 0.42 A |
| MDR-20-5 ratings | Input 100-240 VAC, 0.55 A, 50/60 Hz; output 5 V, 3 A |
| MDR-20-12 ratings | Input 100-240 VAC, 0.55 A, 50/60 Hz; output 12 V, 1.67 A |
| MDR-20-15 ratings | Input 100-240 VAC, 0.55 A, 50/60 Hz; output 15 V, 1.34 A |
| MDR-20-24 ratings | Input 100-240 VAC, 0.55 A, 50/60 Hz; output 24 V, 1 A |
| MDR-40-5 ratings | Input 100-240 VAC, 1.1 A, 50/60 Hz; output 5 V, 6 A |
| MDR-40-12 ratings | Input 100-240 VAC, 1.1 A, 50/60 Hz; output 12 V, 3.33 A |
| MDR-40-24 ratings | Input 100-240 VAC, 1.1 A, 50/60 Hz; output 24 V, 1.7 A |
| MDR-40-48 ratings | Input 100-240 VAC, 1.1 A, 50/60 Hz; output 48 V, 0.83 A |
| MDR-60-5 ratings | Input 100-240 VAC, 1.8 A, 50/60 Hz; output 5 V, 10 A |
| MDR-60-12 ratings | Input 100-240 VAC, 1.8 A, 50/60 Hz; output 12 V, 5 A |
| MDR-60-24 ratings | Input 100-240 VAC, 1.8 A, 50/60 Hz; output 24 V, 2.5 A |
| MDR-60-48 ratings | Input 100-240 VAC, 1.8 A, 50/60 Hz; output 48 V, 1.25 A |
| MDR-100-12 ratings | Input 100-240 VAC, 1.3 A, 50/60 Hz; output 12 V, 7.5 A |
| MDR-100-24 ratings | Input 100-240 VAC, 1.3 A, 50/60 Hz; output 24 V, 4 A |
| MDR-100-48 ratings | Input 100-240 VAC, 1.3 A, 50/60 Hz; output 48 V, 2 A |
Allow 5 mm left and right, 40 mm above, and 20 mm below the unit.
50°C.
TS35/7.5 or TS35/15.
Wires should withstand at least 80°C, such as UL1007.