MEAN WELL DLC-02-KN KNX DALI Gateway Installation Manual

This manual introduces the installation and use of DLC-02-KN KNX to DALI gateway.


MEAN WELL DLC-02-KN KNX DALI Gateway Installation Manual - cover page
Brand
Mean Well
Category
Automation control Equipment
Document type
Installation Guide
Language
English
Pages
100
File format
PDF
File size
2.1 MB
Published
02 November, 2023
Updated
02 November, 2023
MD5 checksum
7C31BD118CCDFD01115D74342F42C465

About this manual

The MEAN WELL DLC-02-KN is a KNX to DALI gateway used to connect a digital DALI lighting system to a KNX installation. It transforms switch and dim commands from the KNX system into DALI telegrams and status information from the DALI bus into KNX telegrams, so room-based lighting control can be incorporated into a higher-level KNX building management system. The device has two independent DALI bus channels with a built-in DALI power supply, can connect up to 2 x 64 DALI ECGs, and includes four 250V/5A relays, an OLED display and LEDs for local operation.

This installation manual covers safety guidelines, device overview and features, displays and operating elements, status LEDs, mechanical specification, mounting on DIN rail, electrical configuration and wiring limits for the DALI and KNX ends, the ETS app (DCA), ETS parameters for general settings, DALI, relays, sequences and timers, DALI commissioning, communication objects, and display functions.

What's inside

  • Safety Guidelines
  • Overview
  • Features
  • Displays and Operating Elements
  • Status LEDs
  • Mounting
  • Electrical Configuration
  • Wiring
  • ETS App (DCA)
  • ETS Parameters

Specifications

DALI Bus Channels2 independent channels with built-in DALI power supply, up to 250 mA per bus
Maximum DALI ECGs2 x 64 DALI ECGs
Maximum ECGs per Bus64
Relay Output4 relays, 250 V / 5 A
Input Voltage100-305 Vac
Scenes and GroupsMax 16 scenes and group setting per channel
Supported DALI Device TypesPart 202/206/207/208/209 (DT1/DT5/DT6/DT7/DT8)
KNX Bus DevicesMax 256 bus devices
KNX Line Segment LengthMax 350 m
DALI Cable LengthMax 300 m with 1.5 mm² cable
ETS CompatibilityETS5 or ETS6

Frequently asked questions

What is the DLC-02-KN used for?

It is a KNX to DALI gateway used to connect a digital DALI lighting system to the KNX installation, converting KNX switch and dim commands into DALI telegrams and DALI status back into KNX telegrams.

How many DALI ECGs can be connected to the gateway?

Up to 2 x 64 DALI ECGs; the maximum is 64 ECGs per bus.

Does the DLC-02-KN support DALI input devices?

No. The manual notes that the DLC-02-KN does not support DALI input devices.

Which ETS versions does the gateway support?

It supports ETS5 or ETS6, and an ETS license is required to enable the DCA page.