Mean Well ICL-R/L AC Inrush Current Limiter Installation Manual

ICL-R/L is an AC inrush current limiter that can be used to reduce the high starting current due to capacitive load or inductive causing the circuit breaker to be false triggered.


Mean Well ICL-R/L AC Inrush Current Limiter Installation Manual - cover page
Brand
Mean Well
Document type
Installation Guide
Language
English
Pages
9
File format
PDF
File size
1.5 MB
Published
20 October, 2023
Updated
20 October, 2023
MD5 checksum
C4B67E2962F4CCA7CCA9CC9D1E717558

About this manual

This manual provides installation instructions for Mean Well's ICL-R/L AC inrush current limiters, including mounting orientation, wiring specifications, and torque settings. It covers models ICL-16R, ICL-16L, ICL-28R, and ICL-28L, with voltage and current ratings of 180-264VAC and 16A or 28A continuous. Safety warnings and environmental conditions are also detailed.

The guide includes diagrams for single-phase and three-phase applications, with specific notes that ICL-16 series is not recommended for three-phase use. It also provides torque values for terminals and wire gauge recommendations based on current load. Environmental compliance declarations for China RoHS, VOC, and TSCA are included in the appendices.

What's inside

  • Introduction
  • Installation
  • Mounting Instructions
  • Wiring Specifications
  • Torque Settings
  • Application Diagrams
  • Safety Warnings
  • Environmental Conditions
  • Compliance Declarations

Specifications

Input Voltage180-264VAC 50/60Hz
Mounting OrientationVertical, input terminals down
Recommended Wire GaugeAWG 18 to 10
Maximum Operating Temperature70°C (ICL-16R/16L) or 60°C (ICL-28R/28L)

Frequently asked questions

What is the maximum operating temperature for ICL-16R/16L?

The maximum operating temperature is 70°C.

What is the recommended torque setting for ICL-16R terminals?

The recommended torque setting is 6.9 kgf-cm (6 Lb-in) for both input and output terminals.

Can ICL-16 series be used for three-phase applications?

No, ICL-16 series is not suggested for three-phase applications.