Instruction manual for MAGPOWR TR-5 Tension Readout, covering installation, setup, electrical connections, calibration, and troubleshooting.
This manual provides step-by-step instructions for installing, setting up, and calibrating the MAGPOWR TR-5 Tension Readout. It details electrical connections, sensor wiring, meter adjustment, and maintenance procedures. Calibration involves adjusting zero and gain using a known weight. Troubleshooting covers issues like inability to zero the meter or incorrect gain output.
The device measures tension in moving webs or strands and can interface with MAGPOWR tension sensors. It supports 0-10 VDC or 4-20 mA DC output signals and operates within a temperature range of 0 to 40°C.
| Supply Voltage | 115/230vac, +/- 10%, 50/60 Hz, Switch selectable |
|---|---|
| Fuses | F1, F2 1.6 amp, Littelfuse Part No. 21601.6, or Wickmann Part No. 19194-053-FS |
| Enclosure | IP20 |
| Operating Temperature | 0º C to 40º C |
| Relative Humidity | 5% to 85% |
| Sensor Excitation | 5 or 10 vdc, 64 madc maximum |
| Tension Sensor Input | 0 to 21 mvdc or 0 to 500 mvdc jumper selectable |
| Outputs | Tension Reference Output: 0 to 10 vdc or 4 to 20 madc |
| Meter Signal | 0 to 1 madc |
The maximum load must be less than or equal to the combined sensor rating and greater than 1/8 of the total sensor rating.
The device supports 115/230 VAC, with a switch selectable for voltage.
The output can be set to 0 to 10 VDC or 4 to 20 mA DC using the 'SELECT OUTPUT' switch.