Kunlun Hai'an JYB-G Explosion-Proof Pressure/Liquid Level Transmitter User Manual

This manual provides installation, wiring, operation, and maintenance instructions for the Kunlun Hai'an JYB-G explosion-proof pressure and liquid level…


Kunlun Hai'an JYB-G Explosion-Proof Pressure/Liquid Level Transmitter User Manual - cover page
Brand
Collihigh
Category
Other Electronics
Document type
User Manual
Language
Chinese
Pages
2
File format
PDF
File size
221 KB
Published
14 March, 2012
Updated
14 October, 2026
MD5 checksum
AF4329162E74D27B8F6C2FA5D3D11617

About this manual

The document is a user manual for the Kunlun Hai'an JYB-G explosion-proof pressure/liquid level transmitter. It details product features such as its international advanced sensor technology and explosion-proof design suitable for industrial process control.

Key sections cover installation requirements, including vertical mounting and the use of pressure buffers for rapid changes. The guide also explains wiring configurations for current (4mA-20mA) and voltage outputs, along with safety precautions for hazardous environments. This manual is written in Chinese.

What's inside

  • Product Features
  • Main Applications
  • Technical Specifications
  • Installation Instructions
  • Wiring Diagrams
  • Trial Operation
  • Safety Precautions
  • Troubleshooting
  • Maintenance

Specifications

Output Form4mA~20mA or 0V~5V
Power SupplyDC 24V (12V~32V)
Accuracy±0.5% or ±0.25%
Medium Temperature Range-30℃ ~85℃
Environmental Temperature Range-20℃ ~85℃
Response Time≤100ms
Load Capacity (Current)≤500 Ω (without display)
Protection RatingIP 65
Explosion Proof RatingExd IIC T6

Frequently asked questions

What is the response time of the JYB-G transmitter?

The response time is less than or equal to 100ms.

How should the transmitter be installed regarding orientation?

Ensure the transmitter is installed vertically relative to the ground.

What type of cable diameter is required for explosion-proof applications?

For explosion-proof ratings, use cables with a diameter between 6mm and 8mm.

How long should the transmitter be preheated before testing?

The transmitter should be powered on and preheated for 15 minutes before pressure testing.