Collihigh JWSK-8 Series Temperature Humidity Transmitter User Manual

The JWSK-8 series temperature and humidity transmitter is an industrial-grade product with multiple analog and network output options. It can measure temperature and humidity in the range of -40℃ to 120℃. Its features include a large LCD display for temperature and humidity, alarm status, zero point correction function, optional relay output, and optional network RS485 or RS232 output.


Collihigh JWSK-8 Series Temperature Humidity Transmitter User Manual - cover page
Brand
Collihigh
Category
Industrial Supply
Document type
User Manual
Language
Chinese
Pages
8
File format
PDF
File size
400 KB
Published
14 March, 2012
Updated
29 September, 2023
Model
V3.5
MD5 checksum
905F42A6D0ED764DDF86C7E7C0E9232C

About this manual

The JWSK-8 series temperature‑humidity transmitter is an industrial‑grade sensor that measures temperature from –40 °C to 120 °C and relative humidity from 0 %RH to 100 %RH. It offers multiple output options (0‑5 V, 0‑10 V, 4‑20 mA, RS485 or RS232) and a 128 × 64 LCD display.

The manual provides detailed installation steps for wall‑mount, pipe‑mount and split‑type units, explains menu navigation, communication settings, alarm configuration, and includes a fault‑diagnosis guide with Modbus protocol examples. This manual is written in Chinese.

What's inside

  • Product Overview
  • Technical Parameters
  • Installation Steps
  • Installation Precautions
  • Operation and Menu Navigation
  • Communication Settings
  • Alarm Configuration
  • Maintenance and Calibration
  • Transport and Storage
  • Fault Diagnosis and Troubleshooting

Specifications

Temperature measurement range-40 °C ~ 120 °C
Humidity measurement range0 %RH ~ 100 %RH
Temperature accuracy±0.5 °C (‑20 °C ~ 60 °C)
Humidity accuracy±3 %RH (0 %RH ~ 100 %RH, 25 °C)
Power supplyDC 24 V (22 V ~ 26 V)
Analog output options0‑5 V, 0‑10 V, or 4‑20 mA
Network output optionsRS485 or RS232
LCD display128 × 64 pixels, shows temperature, humidity, dew point, alarm status
Dimensions (without probe)180 mm × 130 mm × 53 mm
Weight (wall‑mount)≈ 470 g
Weight (pipe‑mount)≈ 750 g

Frequently asked questions

How can I change the communication address of the transmitter?

Press the '/' key to adjust the address value (0‑127) and confirm with the Enter key.

What are the default communication settings for Modbus RTU?

The default settings are COM1, 9600 bps, 8 data bits, 1 stop bit, no parity.

How often should the transmitter be calibrated?

It is recommended to calibrate the transmitter at least once a year to maintain measurement accuracy.

What should I do if the analog output reads zero?

Check that the wiring is correct and secure; a zero output may indicate a wiring error or that the sensor is out of range.

Download PDF (400 KB)