Installation guide for King H series hydronic fan coil heaters, covering mounting, wiring, thermostat compatibility, and safety precautions.
This guide provides step-by-step instructions for installing King H series hydronic fan coil heaters. It includes recommendations for optimal placement, electrical and water line connections, thermostat compatibility, and safety precautions. The document also includes size charts, voltage and current specifications, and BTU output ratings for different models.
Installation requires disconnecting power, ensuring proper grounding, and following local electrical codes. The heater must be mounted at least 4 inches from the floor and positioned to avoid obstructions. Specific thermostat models (King HW/HWP/HWPT-120 or HB/HBP) are required for proper control. This manual is written in Chinese.
| Voltage | 120V |
|---|---|
| Maximum Circuit Amps | 15 Amps |
| Water Temperature Range | 100 to 200 Degree F |
| Water Pressure Rating | up to 125 psi |
| Recommended Mounting Clearance | 4 inches from side walls longer than 18 inches, 8 inches below ceiling or shelf |
Only King model HB / HBP or HW / HWP / HWPT-120 thermostats are designed to control this heater.
Maximum 15 Amps circuit breaker or fusing is required.
The heater should be located a minimum of 4 inches off a finished floor.
Inlet water temperature range is 100 to 200 Degree F.