Installation manual for the IronRidge Flush Mount module mounting system, covering bases, rails, grounding lugs, modules, expansion joints and compatibility.
The IronRidge Flush Mount Installation Manual describes proper installation procedures and required standards for the Flush Mount module mounting system. It covers ratings and markings, a pre-installation checklist, tools and torque values, and IronRidge components.
The manual gives step-by-step procedures for attaching bases, placing rails, securing grounding lugs and modules, and installing expansion joints. It also includes an electrical diagram and notes on FlashFoot2, end caps, wire clips, flush standoffs, microinverter kits, frameless module kits and module compatibility.
| Listing | UL 2703 listed |
|---|---|
| Max OCPD Rating | 25A |
| Max Module Size | 24ft² |
| Module Orientation | Portrait or Landscape |
| Allowable Design Load Rating | 10 PSF downward, 5 PSF upward, 5 PSF lateral |
| Water Seal Ratings | UL 441 & TAS 100-95 (FlashFoot2) |
| Water Seal Roof Slope | 2:12 to 12:12 |
| Grounding Wire Size | Minimum 10 AWG solid or stranded copper |
The maximum module size is 24ft².
The manual specifies torquing the UFO to 80 in-lbs.
Expansion joints are required for rows exceeding 100 feet of rail.
A torque wrench with a 0-250 in-lbs range is required.