Installation instructions for the IronRidge Tilt Mount, covering bases, tilt legs, rails, grounding lugs, modules, torque values, and compatibility.
The IronRidge Tilt Mount Installation Manual describes proper installation procedures and standards for the Tilt Mount. It covers ratings and markings, the pre-installation checklist, required tools, torque values, and IronRidge components.
Steps include attaching bases, adding tilt legs, placing rails, securing lugs and modules, and using CAMO, expansion joints, end caps, wire clips, microinverter kits, and frameless module kits. The manual also provides an electrical diagram and module compatibility information.
| Certification | UL 2703 Listed |
|---|---|
| Max Overcurrent Protective Device Rating | 25A |
| Max Module Size | 25.6 ft² |
| Module Orientation | Portrait or Landscape |
| LTR AE Canadian Load Rating | 2400 PA |
| Class A System Fire Rating | Per UL 2703 |
| Tilt Leg Nut Torque | 250 in-lbs |
| Rail Grounding Lug Nut Torque | 80 in-lbs |
Tighten the Tilt Leg nuts to 250 in-lbs.
The maximum OCPD rating is 25A.
Yes, rails can mount on either the north or south side of the North Tilt Leg.
Use a minimum 10 AWG solid copper or stranded grounding wire.