Hongrun OHR-G500/G500R Series LCD Manual Operator/Recorder User Manual

User manual for Hongrun OHR-G500/G500R series LCD manual operators and recorders, covering installation, wiring, operation, and technical specifications.


Hongrun OHR-G500/G500R Series LCD Manual Operator/Recorder User Manual - cover page
Brand
Hong Run
Category
Automation control Equipment
Document type
User Manual
Language
Chinese
Pages
16
File format
PDF
File size
2.2 MB
Published
09 November, 2026
Updated
09 November, 2026
MD5 checksum
16DC70CEF7D5242CB99A7233ADE06975

About this manual

The Hongrun OHR-G500/G500R series are LCD manual operators and recorders designed as backup instruments for regulators or computer control systems. They accept synchronized setpoint and feedback signals, perform regulation based on external setpoints, output corresponding control signals, and can directly drive valves or work with actuators for solenoid valves, control valves, and inverters.

The instruments feature surface-mount technology, multiple protection and isolation designs for strong anti-interference and high reliability. They include USB data export with up to 720 days of storage, a 3.5-inch backlit dot-matrix LCD, panel touch-key configuration, and support for a wide range of input signals including current, voltage, thermocouples, and RTDs. This manual is written in Chinese.

What's inside

  • Product Introduction
  • Technical Parameters
  • Ordering Information
  • Installation
  • Instrument Operation

Specifications

Measurement input signalsCurrent (0-20mA, 4-20mA, etc.), voltage (0-5V, 1-5V, etc.), thermocouples (B, S, K, E, T, J, R, N, F2, Wre3-25, Wre5-26), RTDs (Pt100, Cu50, Cu53, Cu100, BA1, BA2), linear resistance (0-400Ω)
Analog output signals4-20mA (load ≤480Ω), 0-20mA (load ≤480Ω), 0-10mA (load ≤960Ω), 1-5V (load ≥250kΩ), 0-5V (load ≥250kΩ), 0-10V (load ≥4kΩ)
Switch output typesRelay (AC220V/2A, DC24V/2A), SSR drive (DC12V±2.5V/30mA), SCR trigger (AC400V/0.5A)
Feed outputDC24V±1, load current ≤50mA
Communication interfacesRS485 and RS232, Modbus RTU, baud rate 1200-19200bps, RS485 distance up to 1km, RS232 up to 15m
Measurement accuracy0.2%FS ±1 digit
Setting methodPanel touch keys, password lock, power-off retention
Display3.5-inch backlit 128×64 dot-matrix LCD, Chinese/English, curves, bar graphs
Recording interval options1, 2, 4, 6, 15, 30, 60, 120, 240 seconds
Maximum storage duration3 days at 1s interval to 720 days at 240s interval
Data backupUSB flash drive up to 16GB, SD card up to 16GB
Print interfaceRS-232C, compatible with SP-A40SH series serial printers
Operating environment-10 to 50°C, ≤85% RH, no strong corrosive gases
Power supplyAC 100-240V 50/60Hz or DC 12-36V
Dimensions (W×H×D)Horizontal: 160×80×110mm; Vertical: 80×160×110mm; Square: 96×96×110mm

Frequently asked questions

What input signals does the OHR-G500/G500R support?

It supports current, voltage, thermocouple, RTD, and linear resistance signals.

What recording intervals are available?

The recording interval can be set to 1, 2, 4, 6, 15, 30, 60, 120, or 240 seconds.

What is the maximum data storage duration?

Up to 720 days at a 240-second interval, or 3 days at a 1-second interval.

Which communication protocols and interfaces are provided?

RS485 and RS232 interfaces with Modbus RTU protocol, baud rates from 1200 to 19200 bps.