The Hongrun NHR-TR30 series is an intelligent three-phase phase-angle trigger based on microcontroller technology. It is intended for controlling various industrial furnace loads, including resistance wires, silicon carbide rods, and transformer-stepped-down silicon molybdenum rods and tungsten filaments, and can also be used for motor soft starting.

The manual covers technical parameters, product introduction, instrument panel, DIP switch function selection, terminal and wiring diagrams, and application methods. It covers phase-angle and zero-crossing trigger modes, soft start/soft stop, current feedback limiting and overcurrent alarm, phase-loss, thyristor breakdown and open-load detection, linearized power output, and three-phase four-wire neutral-line selection. This manual is written in Chinese.

What's inside

  • 技术参数
  • 产品介绍
  • 仪表型谱
  • 功能选择说明
  • 接线端子图
  • 接线图
  • 应用方法
  • 运行指示及报警指示
  • 软启动/软停止功能
  • 电流反馈限制及过流报警

Specifications

工作电源AC220V±20%,50Hz±5%
直流电源输出5V及24V两组
工作环境湿度10%~85%RH(无结露)
输入信号电流4~20mA或0~20mA;电压1~5V或0~5V
输出能力驱动可控硅(触发脉冲4V/200mA,0.1mS)
安装方式标准35mm DIN导轨安装
安装尺寸122*82*42 mm(长*宽*高)
软启动/软停止延迟时间1~50秒之间调整
电流反馈报警阈值反馈电流大于量程15%时(输入约为5.75V)
变送器供电24V/25mA
电流变送器响应时间20~40mS左右
IN2延迟调整每输入125mV电压约增加1秒延迟时间
手动功率限制电位器250Ω,功率应大于1/2W
手动功率调节电位器1K电位器
零线线径要求普通电阻丝负载应与相线相同;硅碳棒等负载建议为相线安全截流量的2~3倍

Frequently asked questions

NHR-TR30系列移相触发器可用于哪些负载和应用?

它可适应电阻丝、硅碳棒及变压器降压的硅钼棒、钨丝等工业电炉,也可用于电机软启动的控制。

如何选择移相触发或周波过零触发输出?

通过触发器主板上的六位拔码开关设置,触发类型选择开关置于ON时为移相触发输出,OFF时为周波过零触发输出。

电流反馈功能如何设置和报警?

将拔码开关5置于ON位置时,IN2作为电流限制反馈输入,软启动/软停止时间固定为2秒;当反馈电流大于量程15%时,报警继电器动作。

三相四线制负载的零线应如何选择?

普通电阻丝负载的零线必须采用与相线相同的线径;电阻随温度或老化变化的负载,零线应比相线更粗,最好为相线安全截流量的2~3倍。