Hongrun OHR-D33 Series Three-Phase Phase Sequence Monitoring Relay User Manual

Hongrun OHR-D33 series three-phase phase sequence monitoring relay user manual covering monitoring modes, technical parameters, wiring and application examples.


Hongrun OHR-D33 Series Three-Phase Phase Sequence Monitoring Relay User Manual - cover page
Brand
虹润
Category
RELAY
Document type
User Manual
Language
Chinese
Pages
2
File format
PDF
File size
637 KB
Published
06 November, 2026
Updated
06 November, 2026
MD5 checksum
1E018A987474ABB5E935B7F616EFFFC0

About this manual

This is the Chinese user manual for the Hongrun OHR-D33 series three-phase phase sequence monitoring relay. The device monitors a three-phase network for phase sequence faults and phase loss (open-phase) faults, provides one single-pole double-throw relay output, draws its power from the A, B and C input terminals, and isolates input from output. The manual covers the front panel layout, technical parameters, monitoring modes with timing diagrams, an application diagram and a wiring example.

The relay is designed for 35 mm DIN rail mounting and should be installed as vertically as possible so that heat can escape from inside the instrument. Rated input is 380V AC with an input range of 300V to 480V AC, the relay contact rating is AC250V/6A or DC30V/6A for resistive loads, and the unit meets the GB/T18268 requirement for industrial equipment applications (IEC 61326-1). A QR code on the label gives access to the manual, wiring diagram, register addresses, communication software and other information. This manual is written in Chinese.

What's inside

  • Product Introduction
  • Panel Appearance and Structure Diagram
  • Technical Parameters
  • Monitoring Modes
  • Phase Sequence and Phase Loss Monitoring Timing Diagram
  • Application Diagram
  • Application Example
  • Installation and Dimensions

Specifications

Rated input signal380V AC
Input signal range300V ~480V AC
Output signal1 single-pole double-throw relay
Contact capacityAC250V/6A, DC30V/6A (resistive load)
Power supply300V~480V AC, taken from the A, B, C input terminals
Insulation resistance (input to output)≥100MΩ at 500VDC
Dielectric strength (input to output)2500Vrms for 1 min, no spark
Operating temperature-10~50℃ (no condensation, no icing)
Relative humidity25%~85%RH
Storage temperature-10~60℃ (no condensation, no icing)
Mounting35mm DIN rail
Dimensions22.5*110*115mm (W*H*D)
Electromagnetic compatibilityMeets GB/T18268 industrial equipment application requirements (IEC 61326-1)

Frequently asked questions

What faults does the OHR-D33 series monitoring relay detect?

It monitors a three-phase network for phase sequence faults and phase loss (open-phase) faults.

How is the OHR-D33 relay mounted?

It is mounted on a 35mm DIN rail; install it as vertically as possible so heat can escape from inside the instrument.

What do the indicator lights on the panel show?

The PWR light indicates power, and the RELAY light indicates the relay has operated.

Download PDF (637 KB)

More 虹润 Manuals


View all 虹润 manuals →