Hongrun OHR-E740 Series Four-Loop Digital Display Controller User Manual

User manual for the Hongrun OHR-E740 Series four-loop digital display controller, covering installation, wiring, setup, and parameter configuration.


Hongrun OHR-E740 Series Four-Loop Digital Display Controller User Manual - cover page
Brand
虹润
Category
Monitoring Equipment
Document type
User Manual
Language
Chinese
Pages
12
File format
PDF
File size
1.5 MB
Published
07 November, 2026
Updated
07 November, 2026
MD5 checksum
12632EBFD6279D65CE9F4DD1128F7826

About this manual

The OHR-E740 Series four-loop digital display controller uses surface-mount production and is described as having strong anti-interference capability. It accepts multiple signal types and can be paired with sensors and transmitters to measure and display temperature, pressure, liquid level, speed, force, and other physical quantities. It displays four measurement signals at once and can provide eight separate alarm outputs or four separate transmission outputs, plus RS485/232 communication.

The manual covers technical parameters, installation dimensions and wiring, the display panel and function keys, power-on setup, and primary and secondary parameter settings. It also describes parameter lock levels, alarm and calculation settings, communication baud rate, input type selection, and transmission output configuration. This manual is written in Chinese.

What's inside

  • Overview
  • Technical Parameters
  • Installation
  • Standard Wiring Instructions
  • Display Panel and Function Keys
  • Power-on Setup
  • Parameter Settings
  • Primary Parameter Settings
  • Secondary Parameter Settings
  • Unit Setting Function Code Table

Specifications

Measurement accuracy0.2%FS ±1 digit
Display range-1999 to 9999
Power supplyAC/DC 100–240 V; DC 20–29 V
Operating temperature-10 to 50 °C
Operating humidity≤85%RH
CommunicationStandard MODBUS; RS485 up to 1 km; RS232 up to 15 m
Relay outputAC220V/2A; DC24V/2A

Frequently asked questions

What is the stated measurement accuracy of the OHR-E740 Series?

The stated measurement accuracy is 0.2%FS ±1 digit.

How far can RS485 communication reach?

RS485 communication can reach up to 1 km using the standard MODBUS protocol.

How are all parameters restored to factory defaults?

Set Loc to 577, then in the Loc menu hold the two keys together for 4 seconds.

What happens if no key is pressed while setting parameters?

After 30 seconds, the meter automatically returns to the real-time measurement screen.