This document is a performance addendum (number 3007-0979-001 Revision A) to the Honeywell FS24X User Manual. It replaces the Additional Performance Specifications section and provides typical indoor and outdoor flame response times and detection distances for various fuels at the Very High sensitivity setting.

The addendum also includes a false alarm immunity table showing minimum distances at which the detector did not false alarm when exposed to sources such as direct sunlight, arc welding, electric heaters, and various lamps. Contact information for Honeywell Analytics offices in the Americas, Europe, and Asia Pacific is provided.

What's inside

  • Flame Response Sensitivity
  • False Alarm Immunity
  • Contact Information

Specifications

Indoor detection distance for n-Heptane (6x6 in)90 ft (27 m)
Indoor response time for n-Heptane (6x6 in)5 seconds
Outdoor detection distance for n-Heptane (12x12 in)200 ft (61 m)
Outdoor response time for n-Heptane (12x12 in)4.2 seconds
False alarm immunity minimum distance for continuous arc welding15 ft (5 m)

Frequently asked questions

What is the typical indoor response time for a 6x6 inch n-Heptane fire?

The typical indoor response time is 5 seconds at a distance of 90 ft.

What is the outdoor detection distance for a 12x12 inch n-Heptane fire?

The typical outdoor detection distance is 200 ft (61 m) with a response time of 4.2 seconds.

At what minimum distance does the detector not false alarm from continuous arc welding?

The minimum distance with no alarm is 15 ft (5 m).