Honeywell DT7550UK2 DUAL TEC Anti-Mask Motion Sensor Installation Instructions

Honeywell DT7550UK2 DUAL TEC anti-mask motion sensor installation instructions cover mounting, wiring, setup, walk testing, and product specifications.


Honeywell DT7550UK2 DUAL TEC Anti-Mask Motion Sensor Installation Instructions - cover page
Brand
Honeywell
Category
Monitoring Equipment
Document type
Installation Guide
Language
English
Pages
2
File format
PDF
File size
1.2 MB
Published
23 November, 2026
Updated
23 November, 2026
MD5 checksum
0C9856A8478AF6E25C00C3EA6C9E4550

About this manual

Honeywell DT7550UK2 DUAL TEC anti-mask motion sensor installation instructions describe selecting a mounting location, separating housings, wiring, mounting, initial setup, and walk testing. The document also covers rear tamper, DIP switch settings, LED and relay operation, mask functions, detection patterns, product specifications, and troubleshooting.

Specifications include a 14 m x 18 m detection range, 9.0 to 15.0 VDC power, 24.200 GHz microwave frequency, and an operating temperature from -10 °C to +55 °C. The sensor measures 11.9 cm high, 7.1 cm wide, and 4.2 cm deep and weighs 172 g.

What's inside

  • Mounting Location Guidelines
  • Rear Tamper
  • DIP Switch Settings (SW1)
  • LED Indicators
  • Relay Operation
  • Mask Function
  • Detection Patterns
  • Product Specifications
  • Troubleshooting

Specifications

Detection range14 m x 18 m
Power requirements9.0 - 15.0 VDC; 25 mA typical, 35 mA maximum at 12 VDC
AC ripple3 V peak-to-peak at nominal 12 VDC
Alarm relayEnergized Form A, 30 mA, 24 VDC, 40 ohms maximum
Fault relayDe-energized Form B (NC), 30 mA, 24 VDC
Tamper switchesCover and wall, Form A (normally closed with cover installed), 30 mA, 24 VDC
Microwave frequency24.200 GHz
PIR white light immunity6,500 Lux typical
Fluorescent light filter50 Hz
Operating temperature-10 °C to +55 °C (14 °F to +131 °F)
Relative humidity5% to 95% (non-condensing)
Temperature compensationAdvanced dual slope
Trouble conditionsMicrowave supervision, PIR self-test, temperature compensation, low voltage
PIR fields of view22 long range, 12 intermediate, 6 lower, 4 look-down
SensitivityHigh (pulse count 1): 1-2 steps; Low (pulse count 2): 3-4 steps
Dimensions11.9 cm H x 7.1 cm W x 4.2 cm D
Weight172 g
Packaged product weightApprox. 211 g
AccessoriesSMB-10, SMB-10C, and SMB-10T mounting brackets; curtain lens (P/N 5-532-820-00)
ApprovalsCE PD6662, EN 50131-1, TS 50131-2-4 Security Grade 3, Environmental Class II

Frequently asked questions

What mounting height does the installation guide recommend?

The guide recommends a 2.3 m mounting height.

What wire size is specified for wiring the sensor?

Use 0.2 to 1.3 mm2 wire.

How long does Zone Finder mode last?

Zone Finder mode times out after ten minutes.

What must be done after every power-up?

The sensor must be walk tested after every power up to complete the power-up mask detection test.

Download PDF (1.2 MB)

More Honeywell Manuals