GE AZ45/AZ65 Series packaged terminal air conditioners and heat pumps: model numbers, capacities, power connection kits, dimensions and installation data.
This is the Architects & Engineers Data Manual for the GE Zoneline AZ45/AZ65 Series. It covers AZ45 cooling with electric heat and AZ65 heat pump with backup electric heat, with quick-reference model tables and chassis nomenclature.
The manual also contains power connection kit tables, wall sleeve and sub-base installation dimensions, condensate disposal and ducted installation sections, exterior grilles, product specifications, and a complete accessory list.
| Cooling capacity, AZ45E07DAB at 208 V | 7,000 BTUh |
|---|---|
| EER, AZ45E07DAB at 208 V | 13.4 |
| Cooling watts, AZ45E07DAB at 208 V | 520 |
| Heat pump capacity, AZ65H07DAB at 208 V | 6,100 BTUh |
| Heat pump COP, AZ65H07DAB at 208 V | 4.0 |
| Voltage/phase/frequency, D suffix | 230/208 Volt, single phase, 60 Hz |
| Voltage/phase/frequency, E suffix | 265 Volt, single phase, 60 Hz |
| Nominal cooling capacity codes | 07=7,000 BTUh; 09=9,000 BTUh; 12=12,000 BTUh; 15=15,000 BTUh |
Yes. The manual states that power connection kits are required on all Zoneline chassis; the correct kit is determined by voltage, amperage and connection method.
H indicates a heat pump with electric resistance heat backup.
ICR means Internal Condensate Removal system, listed for AZ65 models only.
They are to be permanently connected in compliance with the National Electrical Code and local codes and have a factory-installed junction box on the chassis.