Installation and operation manual for the Gamewell ZNS microprocessor-based conventional fire alarm control panel with 2 to 32 zones.
This manual from The Gamewell Company covers the installation, programming and service of the ZNS microprocessor based conventional fire alarm control panel and its related modules. The ZNS is designed to monitor 2 to 32 conventional initiation zones and also allows 2 circuits of addressable detection or control devices; it is a supplement to the INS-2 Installation and Programming manuals.
The document describes mechanical mounting and cabinet sizes, wiring, the common card with its indicators, auxiliary power and default operation, and the 31016 two-zone card with its indicators, alarm disconnect switch, low/high current operation, addressing and jumper programming. It also lists power requirements, Appendix A with the high current compatibility identifier and compatible notification devices, and Appendix B with drawing numbers.
| Supported conventional zones | 2 to 32 conventional initiation zones |
|---|---|
| Addressable circuits | 2 circuits of addressable detection or control devices |
| Cabinet size (1 to 16 zones) | 21"W x 25.5"H x 4"D |
| Cabinet size (2 to 32 zones) | 21"W x 31.5"H x 4"D |
| Maximum loop resistance | 25 ohms |
| Auxiliary power total current | 0.5 amps |
| EOL resistor, high current | 4.7K ohms |
| EOL resistor, low current | 15K ohms |
| Common card current draw | 2 mA from +24V, 5 mA from +5V |
| Zone card current draw | 0.5 mA from +5V plus 6.5 mA per trouble or alarm LED |
| Zone current, hi-current in alarm | 60 mA max |
The ZNS is designed to monitor 2 to 32 conventional initiation zones and also allows 2 circuits of addressable detection or control devices.
Zones should be wired in accordance with NFPA 70, article 760, and maximum loop resistance should not exceed 25 ohms.
Auxiliary power is available from terminals A+, A- and resettable smoke detector power from S+, S-, with a combined total of 0.5 amps.
The module is factory set as a high current zone; low current mode is selected by removing resistors R1, R2, R3 for the odd zone or R21, R22, R23 for the even zone.