This file is the user manual of FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER
The Gamewell FIREFORCE 8 Notification Appliance Circuit Expander is a device designed to extend notification appliance circuits. The manual details the general information, functional descriptions, and electrical operating characteristics of the unit. It emphasizes the importance of reading the manual before installation and following proper maintenance guidelines set by the National Fire Protection Association.
| Maximum Total Load | 8 Amps |
|---|---|
| Safety Factor | 1.25 |
The total load of the notification appliance circuit and external load must not exceed 8 Amps.
A safety factor of 25% should be added to the total normal and alarm currents to determine the minimum battery size.