Gamewell IdentiFlex 630 Analog/Addressable Fire Alarm Control Panel Installation and Operation Manual

This manual describes the installation and operation of the identiflex 630 analog/addressable fire alarm control panel.


Gamewell IdentiFlex 630 Analog/Addressable Fire Alarm Control Panel Installation and Operation Manual - cover page
Brand
Gamewell
Category
Other Electronics
Document type
User Manual
Language
English
Pages
226
File format
PDF
File size
1.8 MB
Published
18 October, 2023
Updated
18 October, 2023
MD5 checksum
B9D5AF76DCC6A220CBB65262133BB593

About this manual

This manual provides installation and operation instructions for the Gamewell IdentiFlex 630 Analog/Addressable Fire Alarm Control Panel. It details the system's modular construction, including the common control section, system I/O components, and CPU module. The document outlines proper installation procedures, hardware assembly, and module identification.

What's inside

  • System Description
  • System Overview
  • System Operation
  • Operating Procedures
  • Installation
  • Programming
  • System Test Mode
  • Computer/Laptop Programming
  • System Monitoring & Control
  • Specifications

Specifications

Quiescent Current275 mA
Alarm Current407 mA plus Signal Circuit power plus 2mA for master box or 22 mA for reverse polarity connections
Input Power24VDC
Maximum Analog Devices504
Field Wiring Terminals12 point

Frequently asked questions

What are the default operating conditions for the IdentiFlex 630?

The default mode is Normal Quiescent Condition, which is the default state of the system.

How does the system verify an alarm condition?

The system automatically verifies the device after a 45 to 60 second reset/stabilization delay and monitors the device for 60 seconds.

What is the nominal sensitivity of the XP95-M Analog Addressable Multisensor Detector?

The XP95-M has a nominal, fixed sensitivity of 2.4%/ft.