This manual introduces the basic functions and operating methods of the S3 series products.
The S3 Series is a small addressable fire alarm control panel that can be used in standalone or networked configurations. It supports one or two signaling line circuits, four Class B notification appliance circuits, and optional network interface boards for integration with other Gamewell‑FCI devices.
The manual covers programming with CAMWorks software, wiring diagrams for the FLPS‑7 power supply, battery installation, periodic testing procedures required by NFPA 72, and warranty information. It also lists optional modules such as LCD displays, digital alarm communicators, and fiber‑optic interfaces.
| FLPS-7 Input Voltage (120 V) | 120 V AC, 60 Hz, Max. 2.75 Amps |
|---|---|
| FLPS-7 Input Voltage (240 V) | 240 V AC, 50/60 Hz, Max. 1.4 Amps |
| Recommended Battery | BAT 12120 batteries (no lithium) |
Programming must be done with the CAMWorks™ software by a Gamewell‑FCI factory‑certified technician; it cannot be programmed from the display panel.
The FLPS‑7 can draw up to 2.75 A at 120 V AC (60 Hz) or up to 1.4 A at 240 V AC (50/60 Hz).