User manual for Flowline's XP88 & XP89 ultrasonic level transmitters, covering installation, configuration, safety, and wiring in hazardous environments.
This manual provides step-by-step instructions for installing, configuring, and operating the Flowline EchoSafe® XP88 and XP89 ultrasonic level transmitters. It covers setup via push-button menu, wiring, safety precautions, and troubleshooting. The transmitters are designed for hazardous environments and offer non-contact liquid level measurement up to 32.8’ (10m) with 4-20 mA output.
Key features include configurable units (inches, feet, meters, percent), fail-safe current output options, and compatibility with NEMA 4 enclosures. The manual also includes mounting guidelines, material compatibility notes, and safety warnings for hazardous area use.
| Range | XP88: 8" to 26.2' (20 cm to 8 m); XP89: 8" to 32.8' (20 cm to 10 m) |
|---|---|
| Accuracy | ± 0.2% of max. range |
| Resolution | 0.079” (2 mm) |
| Beam Width | 3" (7.6 cm) dia. |
| Display Type | LCD, 6-digit |
| Supply Voltage | 18-28 VDC (loop) |
| Signal Output | 4-20 mA, two-wire |
| Enclosure Rating | NEMA 4 |
| Process Mount | 2” NPT |
| Compliance | CE, RoHS |
| Classification | Explosion proof |
XP88: 8" to 26.2' (20 cm to 8 m); XP89: 8" to 32.8' (20 cm to 10 m).
The fail-safe output can be set to 4mA (Empty), 20mA (Full), 21mA, 22mA (Overfill), or Hold Last Value.
Yes, use the REV MA setting to reverse the 4mA (bottom) and 20mA (top) positions.