Operating manual for the Endress+Hauser Prosonic T FMU30 ultrasonic level transmitter, covering installation, wiring, setup, diagnostics and technical data.
This operating manual describes the installation and commissioning of the Endress+Hauser Prosonic T FMU30 ultrasonic level transmitter. It covers the functions needed for routine measurement operation, while additional parameters such as measurement point optimization and measured value conversion are referenced to the separate instrument function description.
The document includes safety guidance, identification and ordering information, installation and wiring, operation via the local display or FieldCare, basic calibration, envelope curve evaluation, troubleshooting, maintenance and repair, accessories, and technical specifications. This manual is written in Chinese.
| Measurement principle | Continuous, non-contact level measurement |
|---|---|
| Maximum range, liquids | 8 m (26 ft) |
| Maximum range, solids | 3.5 m (11 ft) |
| Output signal | 4...20 mA |
| Supply voltage | 14...35 V |
| Power consumption | 51...800 mW |
| Terminal cable cross-section | 0.25...2.5 mm (20...14 AWG) |
| Cable entry | M20x1.5 cable gland, G½ or ½ NPT |
| Protection rating | IP68 |
| Sensor options | 1½" or 2" sensor |
| Blind distance, 1½" sensor | 0.25 m |
| Blind distance, 2" sensor | 0.35 m |
| Measured variable | Distance D between sensor diaphragm and material surface |
The maximum range is 8 m (26 ft) for liquids and 3.5 m (11 ft) for solids, depending on the sensor used.
The instrument provides a 4...20 mA output signal, with an adjustable current output and an alarm signal shown on the local display.
The supply voltage is 14...35 V; explosion-proof instruments may have additional limits stated in the relevant safety instructions.
It can be operated through the local display with keys or through FieldCare, as described in the operation section.