This manual covers the installation, operation, maintenance, and troubleshooting of the Emerson RTJ-N series indirect-acting gas regulator for natural gas…
The document provides a comprehensive guide for the Emerson RTJ-N Series Gas Regulator, an indirect-acting device designed for regional pressure regulation or industrial/commercial applications. It covers various gas types including natural gas, manufactured gas, and liquefied petroleum gas.
Key sections include model specifications, technical parameters such as maximum inlet pressure (0.8 MPa) and flow coefficients, structural details with dimensional drawings, flow calculation formulas for different gases, and detailed instructions for installation, commissioning, and maintenance procedures. This manual is written in Chinese.
| Maximum Inlet Pressure | 0.8 MPa |
|---|---|
| Inlet Pressure Range | 0.02~0.8 MPa |
| Outlet Pressure Range | 0.01~0.4 MPa |
| Stabilization Accuracy (AC) | Up to AC5 |
| Pressure Rating (SG) | Up to SG10 |
| Operating Temperature Range | -10~60°C / 14~140°F |
It is suitable for natural gas, manufactured gas, liquefied petroleum gas, and other non-corrosive gases.
Rubber parts should be inspected and replaced every 3 to 6 months depending on gas quality usage.
Close the inlet and outlet valves, open the small vent valve between the regulator and valves to release internal pressure.