E 1454H001 Multistage Regulator User Manual

User manual for the E 1454H001 multistage regulator with 4-20 mA and NTC inputs, four relay stages, and compressor central control.


E 1454H001 Multistage Regulator User Manual - cover page
Brand
E
Category
Automation control Equipment
Document type
User Manual
Language
Spanish
Pages
2
File format
PDF
File size
171 KB
Published
17 November, 2026
Updated
17 November, 2026
MD5 checksum
2DAFDB0CDC06B80746FCB6640859E9C0

About this manual

The E 1454H001 is a multistage regulator designed to display, control, and regulate compressor centrals using 4-20 mA and NTC probe inputs. It provides four relay outputs that can be configured as four independent stages or two partialized stages, plus a switched alarm relay and six voltage-free digital inputs.

The manual covers panel mounting, wiring, parameter configuration through three programming levels, and relay control modes including balanced, sequential, proportional, and neutral zone operation. It also describes thermal, high-pressure, and low-pressure alarm inputs and the associated safety timing. This manual is written in Spanish.

What's inside

  • 1- Instalación
  • 1.1- Montaje panel
  • 1.2- Conexionado
  • 2- Configuración
  • 2.1 Configuración de parámetros
  • Nivel 1 Menús
  • Nivel 2 Parámetros
  • Nivel 3 Valores
  • 3- Funcionamiento
  • 3.1 Control de relés

Specifications

Inputs4-20 mA and NTC
Relay outputs4 relays
Panel cutout70.5 x 28.5 mm
Alarm outputSwitched relay for alarm
Digital inputsSix voltage-free digital inputs
Thermal alarm inputsFour
High-pressure alarm inputOne
Low-pressure alarm inputOne
Stage configuration4 independent stages or 2 partialized stages
Protection ratingIP65 with correct gasket installation

Frequently asked questions

How is Level 1 menu programming accessed?

Press the N and Q keys simultaneously for 10 seconds; the PR LED flashes intermittently and the first menu PSP appears.

What happens if no key is pressed for 25 seconds during programming?

The controller automatically returns to value display without changing the parameter values.

How can the four relay stages be configured?

They can be configured for four independent stages or two partialized stages.

What does neutral zone mode do?

Within the defined neutral zone, stages keep their previous state; stages turn on above the upper limit and turn off below the lower limit.