Donaldson mist collector preventative maintenance schedule covering fan exhaust, drainage, filter pressure drop, afterfilter, and fan checks.
This document is a preventative maintenance schedule for Donaldson mist collectors. It lists tasks for checking fan exhaust, monitoring mist drainage, recording collector and afterfilter pressure drops, inspecting pneumatic lines, and checking fan and motor.
The schedule includes intervals for daily, weekly, monthly, every six months, and every three months. It also notes an important notice about factors affecting product use and performance, and directs users to consult the Installation and Operation Manual for troubleshooting.
| New filter pressure drop | Less than 1” w.g. |
|---|---|
| Normal filter pressure drop | 1 to 6” w.g. |
| Afterfilter pressure drop increase | Approximately .25” w.g. per month |
Initially, monitor the drainage system daily, then weekly once you are sure it is operating properly.
Generally 1 to 6” w.g. is considered normal.
Verify proper system airflow according to original design recommendations, and change filters if necessary.