Donaldson mist collector preventative maintenance schedule covering fan exhaust, drainage, filter pressure drop, afterfilter, and fan checks.


Donaldson Mist Collectors Preventative Maintenance Manual - cover page
Brand
Donaldson
Category
Industrial Supply
Document type
Service Manual
Language
English
Pages
2
File format
PDF
File size
74 KB
Published
23 November, 2026
Updated
23 November, 2026
MD5 checksum
0C8EB53FAD44B98920A612C413EED128

About this manual

This document is a preventative maintenance schedule for Donaldson mist collectors. It lists tasks for checking fan exhaust, monitoring mist drainage, recording collector and afterfilter pressure drops, inspecting pneumatic lines, and checking fan and motor.

The schedule includes intervals for daily, weekly, monthly, every six months, and every three months. It also notes an important notice about factors affecting product use and performance, and directs users to consult the Installation and Operation Manual for troubleshooting.

What's inside

  • Exhaust of fan to ensure filter integrity
  • Mist drainage system
  • Collector filter pressure drop
  • HEPA/DOP afterfilter pressure drop
  • Filter pressure drop pneumatic lines
  • Check fan and motor
  • Adjust exhaust damper as needed
  • Pulse diaphragms

Specifications

New filter pressure dropLess than 1” w.g.
Normal filter pressure drop1 to 6” w.g.
Afterfilter pressure drop increaseApproximately .25” w.g. per month

Frequently asked questions

How often should the mist drainage system be monitored?

Initially, monitor the drainage system daily, then weekly once you are sure it is operating properly.

What is considered normal filter pressure drop?

Generally 1 to 6” w.g. is considered normal.

What should be done if filter element pressure drop exceeds 6”w.g.?

Verify proper system airflow according to original design recommendations, and change filters if necessary.