Celduc SUL963460 Single Phase Power Solid State Relay Datasheet

Celduc SUL963460 single-phase power solid state relay datasheet covering specifications, thermal curves, protection and installation notes.


Celduc SUL963460 Single Phase Power Solid State Relay Datasheet - cover page
Brand
CELDUC
Category
RELAY
Document type
Datasheet
Language
French
Pages
5
File format
PDF
File size
1.3 MB
Published
09 November, 2026
Updated
09 November, 2026
MD5 checksum
1F1AF4335D853B52BFCF6FEFAB743AEB

About this manual

The Celduc SUL963460 is a 22.5 mm single-phase power solid state contactor/relay intended for resistive loads (AC-51). It uses back-to-back thyristors with TMS2 technology and has a 24–600 VAC output range, a 3.5–32 VDC control range, a two-point pluggable control connector, a yellow input LED and input over-voltage protection. The relay must be mounted on a heatsink.

The datasheet gives input and output characteristics, thermal curves and heatsink selection, overload current curves and short-circuit protection coordination with a FERRAZ gRC 25 A 14 x 51 fuse. It also lists IP20 terminal protection, conformity with IEC/EN60947-4-3, EN60950/VDE0805, IEC 60335-1/VDE0700-1 and UL-cUL, and warns that semiconductor relays do not provide galvanic isolation between the load and the mains. This manual is written in French.

What's inside

  • Control characteristics
  • Output characteristics
  • General characteristics
  • Thermal curves and heatsink choice
  • Overload currents
  • Short circuit protection coordination
  • CE and US conformity
  • Typical application

Specifications

Product typeSingle-phase power solid state contactor
Width22.5 mm
Output voltage range24–600 VAC
Thyristor size35 A
Current limitation by heatsink21/32 A
Control voltage range3.5–32 VDC
Control connector2-point pluggable
Input LEDYellow
Terminal protectionIP20 with removable flaps
Typical application8 kW resistor at 400 VAC (AC-51)
Short-circuit protection coordinationFERRAZ gRC 25 A, 14 x 51 mm fuse
Housing/base materialPA 6 UL94VO housing; aluminum base plate
CE/US conformityIEC/EN60947-4-3; UL/cUL

Frequently asked questions

What type of load is the Celduc SUL963460 intended for?

It is designed for resistive loads (AC-51).

Must the SUL963460 be mounted on a heatsink?

Yes. The document states that the SSR must be mounted on a heatsink.

What is the control voltage range of the SUL963460?

The control range is 3.5–32 VDC with an input current limiter.

Does the SUL963460 provide galvanic isolation between the load and the mains?

No. The document warns that semiconductor relays do not provide galvanic isolation between the load and the mains.

Download PDF (1.3 MB)

More CELDUC Manuals


View all CELDUC manuals →