Celduc SUL963460 single-phase power solid state relay datasheet covering specifications, thermal curves, protection and installation notes.
The Celduc SUL963460 is a 22.5 mm single-phase power solid state contactor/relay intended for resistive loads (AC-51). It uses back-to-back thyristors with TMS2 technology and has a 24–600 VAC output range, a 3.5–32 VDC control range, a two-point pluggable control connector, a yellow input LED and input over-voltage protection. The relay must be mounted on a heatsink.
The datasheet gives input and output characteristics, thermal curves and heatsink selection, overload current curves and short-circuit protection coordination with a FERRAZ gRC 25 A 14 x 51 fuse. It also lists IP20 terminal protection, conformity with IEC/EN60947-4-3, EN60950/VDE0805, IEC 60335-1/VDE0700-1 and UL-cUL, and warns that semiconductor relays do not provide galvanic isolation between the load and the mains. This manual is written in French.
| Product type | Single-phase power solid state contactor |
|---|---|
| Width | 22.5 mm |
| Output voltage range | 24–600 VAC |
| Thyristor size | 35 A |
| Current limitation by heatsink | 21/32 A |
| Control voltage range | 3.5–32 VDC |
| Control connector | 2-point pluggable |
| Input LED | Yellow |
| Terminal protection | IP20 with removable flaps |
| Typical application | 8 kW resistor at 400 VAC (AC-51) |
| Short-circuit protection coordination | FERRAZ gRC 25 A, 14 x 51 mm fuse |
| Housing/base material | PA 6 UL94VO housing; aluminum base plate |
| CE/US conformity | IEC/EN60947-4-3; UL/cUL |
It is designed for resistive loads (AC-51).
Yes. The document states that the SSR must be mounted on a heatsink.
The control range is 3.5–32 VDC with an input current limiter.
No. The document warns that semiconductor relays do not provide galvanic isolation between the load and the mains.