Celduc SO942960 Single Phase Power Solid State Relay Datasheet

Celduc SO942960 single phase power solid state relay datasheet covering output, control, thermal, wiring and installation specifications.


Celduc SO942960 Single Phase Power Solid State Relay Datasheet - cover page
Brand
CELDUC
Category
RELAY
Document type
Datasheet
Language
French
Pages
5
File format
PDF
File size
415 KB
Published
09 November, 2026
Updated
09 November, 2026
MD5 checksum
16E2F7C1EFAF263F2581DE4833016B01

About this manual

The Celduc SO942960 is a single phase power solid state relay in the okpac range. It is a zero cross relay intended for resistive loads (AC-51), with an output of 12 to 280 VAC at 25 A and a control voltage range of 185 to 265 VAC/DC. A green LED indicates the input, and IP20 protection is provided by removable terminal flaps.

The document gives output, control and general characteristics, thermal curves and heatsink selection, overload current data, control and power wiring, and terminal and label details. It states that the SSR must be mounted on a heatsink and that semiconductor relays do not provide galvanic insulation between the load and the mains, so an adapted circuit breaker with insulation feature or similar device must be used. This manual is written in French.

What's inside

  • Output characteristics
  • General characteristics
  • Control characteristics
  • Thermal curves and heatsink choice
  • Overload currents
  • Control wiring
  • Power wiring
  • IP20 flaps
  • Labels
  • Dimensions

Specifications

Output12 to 280 VAC, 25 A
Control voltage range185 to 265 VAC/DC
Load typeResistive loads (AC-51)
Typical application4 kW resistor at 230 VAC
Protection levelIP20
Standards conformityEN60947-4-3 (IEC947-4-3), UL/cUL
Short circuit protection fuseFERRAZ gRC 25A 14x51
Control wiring wire range0.75 to 2.5 mm² (AWG18 to AWG14)
Power wiring wire range1.5 to 10 mm² (AWG16 to AWG8)
M5 screw tightening torqueMin 2 / Typ 2.4 / Max 3 N·m

Frequently asked questions

What is the output voltage and current rating?

The relay has an output of 12 to 280 VAC at 25 A.

What control voltage range does the SO942960 accept?

It accepts 185 to 265 VAC/DC.

Does the relay need a heatsink?

Yes, the relay must be mounted on a heatsink.

What kind of load is the relay designed for?

It is designed for resistive loads (AC-51), such as a 4 kW resistor on 230 VAC.

Download PDF (415 KB)

More CELDUC Manuals


View all CELDUC manuals →