This guide describes the mechanical and electrical installation of the ACSM1-04 drive module (0.75 to 45 kW)


ABB ACSM1-04 Drive Module Quick Installation Guide - cover page
Brand
ABB
Category
Other
Document type
Installation Guide
Language
Chinese
Pages
8
File format
PDF
File size
879 KB
Published
29 September, 2011
Updated
30 September, 2023
MD5 checksum
1AC4F486624B99141BBDA50F8AC89E69

About this manual

This guide describes the mechanical and electrical installation of the ABB ACSM1-04 drive module for 0.75 to 45 kW. It includes safety precautions, installation design requirements, mechanical mounting, power and control cable connections, wiring diagrams, and terminal settings.

The drive module has an IP20 protection rating for controlled indoor environments. Installation requires disconnecting power and waiting at least 5 minutes before work, and the guide specifies cable shielding, grounding, and tightening torque requirements for different model ranges. This manual is written in Chinese.

What's inside

  • Introduction
  • Safety precautions
  • Installation design
  • Mechanical installation
  • Electrical installation
  • Wiring diagram
  • Power terminal cable specifications
  • Tightening torques
  • Control cable connection

Specifications

Protection ratingIP20 (UL open type)
Maximum ambient temperature at rated current40 °C (104 °F)
Current derating temperature range41 to 55 °C (104 to 131 °F)
Circuit capacityPeak current up to 100,000 rms, maximum 480 V
Motor-circuit cable derating temperature75 °C (167 °F)
Input cable protectionFuse or circuit breaker
X1 external input power24 V DC, 1.6 A
X2 relay output250 V AC / 30 V DC, 2 A
Maximum total current200 mA

Frequently asked questions

How long must I wait after disconnecting power before working on the ACSM1-04?

At least 5 minutes must be allowed for the intermediate circuit capacitors to discharge.

What is the protection rating of the ACSM1-04 drive module?

It is IP20 (UL open type).

What is the maximum ambient temperature at rated current?

40 °C (104 °F).

What tightening torque is used for power terminals on ACSM1-04xx-024A to 090A-4 models?

3 N·m (25 lbf·in), or 15 N·m (11 lbf·ft).

Download PDF (879 KB)

More ABB Manuals