Aertai ZigBee1082 Wireless Data Acquisition Card User Manual


Aertai ZigBee1082 Wireless Data Acquisition Card User Manual - cover page
Brand
Beijing阿尔泰发展
Category
Automation control Equipment
Document type
User Manual
Language
Chinese
Pages
7
File format
PDF
Published
23 September, 2011
Updated
29 September, 2023
MD5 checksum
9F14C4AEA6A481E2FBAD40C32E63D6B9

About this manual

The manual describes the ZigBee1082 wireless data acquisition card from Aertai Technology, including terminal wiring, DIP switch settings, LED indicators, and a temperature sensor for thermocouple cold-junction compensation. It lists supported thermocouple input types and key electrical specifications.

The document also provides MODBUS protocol address maps and command examples for reading holding registers, reading input registers, setting a single holding register, and setting multiple holding registers. Version 6.010 is shown on the manual pages. This manual is written in Chinese.

What's inside

  • Module structure and wiring terminals
  • Main performance specifications
  • Baud rate configuration code table
  • Analog input type configuration code and error table
  • MODBUS protocol address allocation table
  • Read holding registers
  • Read input registers
  • Set single holding register
  • Set multiple holding registers

Specifications

Input typeThermocouple J, K, T, E, R, S, B, N, WRe5-WRe26
Channel input8 differential channels
Sampling frequency10 Hz
Resolution16 bit
Input impedance20 MΩ
Isolation voltage3000 V
Power supplyUnprocessed +10 V to +30 VDC
Power consumption0.6 W @ 24 VDC when XBEE network data transmission is not used
K-type thermocouple accuracyTypical ±0.5°C, maximum ±0.9°C

Frequently asked questions

How do I restore the ZigBee1082 module to its default configuration?

Short the INIT pin to GND before powering the module, then power it on. The module restores the default address 1 and baud rate 9600.

What do the three LED indicators on the ZigBee1082 module mean?

The green LED is the power indicator, the yellow LED is the network indicator, and the red LED is the communication indicator.

What power supply does the ZigBee1082 module require?

It uses an unprocessed +10 V to +30 VDC power supply.

How can I configure the internal XBEE module?

Set SW1 positions 1 and 3 to ON and 2 and 4 to OFF, connect the module's RS232 port to a computer, and use DIGI X-CTU software.