This fire alarm system manual describes the features and specifications of the FMM-325A analog manual station. The product complies with the Americans with Disabilities Act ADA 4.28.3 and the National Fire Protection Association NFPA 72.
Bosch FMM-325A analog manual stations are used in the polling circuit of compatible Bosch fire alarm control panels. They communicate power and data over a two-wire circuit, and the alarm lever latches in the pulled position.
The document lists certifications, compatibility, mounting notes, included parts, electrical and environmental specifications, and ordering information for the single-action and double-action models.
| Alarm current | 28 mA |
|---|---|
| Polling current | 22 mA ± 20% |
| Standby current | 0.35 mA typical |
| Input voltage | 24 VDC nominal |
| Operating voltage | 17 VDC to 41 VDC |
| Operating temperature | +14°F to +120°F (-10°C to +49°C) |
| Activation force | 5 lb (2.3 kg) |
| Dimensions (H x W x D) | 4.75 in. x 3.2 in. x 0.875 in. (12.1 cm x 8.1 cm x 2.2 cm) |
| Material | Painted die-cast metal |
They are used with FPA-1000 Analog Addressable Fire Panels and the D9024, D8024, and D10024A Fire Alarm Control Panels.
The address is set by programming an EEPROM microchip with the D5070 Analog Device Programmer.
No, these manual stations are for indoor use only.