NDC1T-4011~6511 Special series AC contactor is used in AC 50Hz(or60Hz),rated insulation voltage is up to 690V,and rated current 40~65A under rated voltage415V and category AC-3 circuit,for long-distance making and nreaking circuit,and can interoperable with the ap
This document is the Version 3 User Manual for the Liangxin NDC1T-40~65 Series Special AC Contactor. It provides instructions for the operation, installation, and maintenance of the device, which is designed for use in circuits with high dust levels and poor working conditions, such as welding and textile industries. The manual includes technical parameters, circuit diagrams, and dimensions for the main unit and accessories.
| Rated working current (AC-3, 415V) | 40~65A |
|---|---|
| Rated insulation voltage | 690V |
| Rated control voltage | 24, 36, 48, 110, 200, 220, 230, 380, 400, 415, 440V |
| Pull voltage | 0.85Us~1.1Us |
| Release voltage | 0.20Us~0.75Us |
| Mechanical life span | 800 x 10^4 times |
It is used in circuits requiring long-distance making and breaking, often with thermal overload relays, specifically in industries with high dust like welding and textile.
Place the NF1 on the corresponding bracket and move it down along the main body until a 'PA' sound is heard.
The maximum wiring torque is 2.5 to 5 N.m.